Indian Boiler Regulations, 2026 · Chapter 10 · Electrode Boilers
Regulation 350. Unstayed flat end plates
Not yet checked against the official Gazette; verify before relying on it.
350. Unstayed flat end plates.─ (1) The working pressure of unstayed flat-end plates shall be determined as per the following formula:
2S(t - 2)² Equation (10/2)
P = -------------
where, t =
D²
thickness of plate in thirty-seconds of an inch,
P = working pressure in pounds per square inch,
D = diameter in inches of the pitch circle of the bolts or rivets when the plate is attached to an
outside flange or the internal diameter of the shell when the plate is attached to an inside flange,
S = minimum tensile stress of the plate in tons per square inch.
(2)In no case the thickness of an unstayed flat-end plate shall be less than 10 mm.
(3)Compensation is not required where an unstayed flat-end plate is pierced for electrodes or other fittings by opening having a diameter not greater than 63 mm and the pitch of the openings is not less than four times of the diameter of the openings.
(4)Where the diameter of the opening in an unstayed flat end plate is greater than 63 mm or the pitch is less than four times the diameter of the holes, full compensation shall be provided as in regulation179.
Tables and formulae are shown in their extracted layout. Alignment, superscripts and subscripts may be lost. The Gazette page image is authoritative.
In short
Regulation 350 sets the working pressure formula, minimum thickness and opening rules for unstayed flat end plates of electrode boilers.
Key points
- (1) Equation (10/2) gives the working pressure P (in pounds per square inch) from the plate thickness t (in thirty-seconds of an inch), the minimum tensile stress S (in tons per square inch) and D. D is the pitch circle diameter of the bolts or rivets when the plate is attached to an outside flange, or the internal diameter of the shell when attached to an inside flange, in inches.
- (2) An unstayed flat end plate must never be less than 10 mm thick.
- (3) No compensation is needed for openings for electrodes or other fittings not greater than 63 mm in diameter, if their pitch is not less than four times the opening diameter.
- (4) If an opening exceeds 63 mm in diameter, or the pitch is less than four times the hole diameter, full compensation is required as in regulation 179.
Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.
Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).
Orientation hints (unverified)
These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.
| Historical 1950-edition reg. | Heading as OCR'd | Heading similarity | Source image |
|---|---|---|---|
| 33 | Plates | 100% | Chapter II (DPIIT scan), image 3 |
| 113 | Flat End Plates | 100% | Chapter III (DPIIT scan), image 2 |
| 412 | Unstayed Flat | 100% | Chapter X (DPIIT scan), image 4 |
Amendment history of the candidate IBR 1950 regulations: Reg. 113 (1 amendment)
IBR 1950 regulation 33 as last published in the DPIIT web edition (archived 2022)
Unofficial archived copy, not verified; see the regulation 33 page for its amendments.
| Reg. 33 MATERIALS OF CONSTRUCTION COPPER PLATES, STAY AND RIVET BARS |
| (a) Process.- The copper shall be fire-refined or electrolytic and hot-rolled from suitable cakes. (b) Chemical Composition.- The chemical composition of the plates shall be as follows:-
(c) Freedom from defects.- The plates shall be clean, smooth and free from defects and shall have a workmanlike finish. They shall be thoroughly annealed. (d) Rolling Margin.- No plate shall be under the specified thickness at any part, not more than 5% over the calculated weight. The scrap margin, partly sheared and left attached, shall be not less than 3 inches at the ends and 1½ inches at each side. (e) Tensile Tests.- One tensile test shall be taken from each plate as rolled. The tensile breaking strength, from Standard Test Piece A, shall not be less than 14 tons per sq. inch with an elongation of not less than 35%. (f) Hot and Cold Bend tests.- One hot (temperature between 1200°F and 1400°F) and one cold bend test shall be taken from each plate as rolled. For either hot or cold bend tests, the test piece shall withstand being doubled over without fracture until the sides are touching and parallel. |
IBR 1950 regulation 113 as last published in the DPIIT web edition (archived 2022)
Unofficial archived copy, not verified; see the regulation 113 page for its amendments.
| Reg. 113 END PLATES Flat End Plates
|
IBR 1950 regulation 412 as last published in the DPIIT web edition (archived 2022)
Unofficial archived copy, not verified; see the regulation 412 page for its amendments.
| Reg. 410, Reg. 411, Reg. 412
Reg. 411
Reg. 412
|
Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.


Indian Boiler Regulations, 2026, reg. 350, Regulation 350, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.736–737. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).
The citation refers to the government publication. Cite the Gazette, not this website.