Regulation 503 — Maker’s Certificates for Steel Economisers

Unofficial DPIIT web edition · not verified1 amendment found

Text in the DPIIT web edition

Archived copy captured 03 Aug 2022 (Wayback Machine); the same page also prints regulations 502, 504. The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.

Unofficial DPIIT web edition · archived 2022 · not checked against the Gazette

Reg. 502, Reg. 503, Reg. 504
STANDARD CONDITIONS FOR THE DESIGN AND CONSTRUCTION OF ECONOMISER, FEED PIPES, FEED HEATERS AND OTHER SIMILAR VESSELS

ECONOMISERS

Modification of formula

Where no certificates are produced, the working pressure as found by formula will be reduced by 10%. When the workmanship is, however, in any way doubtful and the Chief Inspector is not satisfied that any of the foregoing conditions would be sufficient to meet the circumstances he may at his discretion reduce the working pressure by such percentage as he deems fit.



Reg. 503
STANDARD CONDITIONS FOR THE DESIGN AND CONSTRUCTION OF ECONOMISER, FEED PIPES, FEED HEATERS AND OTHER SIMILAR VESSELS

ECONOMISERS

Maker’s Certificates for Steel Economisers

The Maker shall furnish the Inspecting Officer with a certificate in the following form:-

“We hereby certify that the material described below has been made by the Open Hearth or an Electric process acid/basic and has been satisfactorily tested in the presence of the Inspecting Officer/our Test House Manager in accordance with the Standard Tests.”



Reg. 504
STANDARD CONDITIONS FOR THE DESIGN AND CONSTGRUCTION OF ECONOMISER, FEED PIPES, FEED HEATERS AND OTHER SIMILAR VESSELS

ECONOMISERS

Hydraulic test for new economisers

For all new economisers the hydraulic test must be applied as shown below:-

On Components before assembly
Design pressure lbs/sq. in.
Hydraulic test pressure lbs./sq.in.
Cast iron tubes, headers and bends
Twice working pressure minimum pressure, 700.

Steel tubes and bends

500 or less

Above 500 but not exceeding 1,000

Above, 1000

1,000

Twice the working pressure

1,000 above the working pressure.

Headers Below 1,000

Above 1,000

Twice the working pressure.

Working pressure plus 1,000 lbs./sq.in.

For all assembled sections the Hydraulic Test pressure shall be not less than 1 ½ times the working pressure.

“Working pressure” shall be the highest pressure at which the economiser relief valves are to be set.

The above test pressure shall be held for a minimum period of ten minutes.

Earlier text: the 2008 DIPP web edition

STANDARD CONDITIONS FOR THE DESIGN AND CONSTRUCTION OF ECONOMISER, FEED PIPES, FEED HEATERS AND OTHER SIMILAR VESSELS

ECONOMISERS

Maker’s Certificates for Steel Economisers

The Maker shall furnish the Inspecting Officer with a certificate in the following form:-

“We hereby certify that the material described below has been made by the Open Hearth or an Electric process acid/basic and has been satisfactorily tested in the presence of the Inspecting Officer/our Test House Manager in accordance with the Standard Tests.”

Amendments found

Machine-assisted list from the amending notifications (DPIIT copies; 1990–1998 from scanned Gazette issues on India Code); may be incomplete.

DateNotificationPartActionWhat changed (summary)Web edition
2010-10-07G.S.R. 821(E)AmendedSubstitutes 'Competent Person' for the Inspecting Officer references.listed before the capture