BETAIndependent engineering reference. Source-text verification is ongoing.Verification ongoing.Verification status →
IBRsourceIndian Boiler Regulations, made clear

Indian Boiler Regulations, 2026 · Chapter 11 · Standard Conditions for the Design and Construction of Economisers, Feed Pipes, Feed Heaters and Other Similar Vessels

Regulation 383. Procedure for Hydraulic Test

Official text — not yet verifiedGazette 1 Oct 2026 · printed pp. 753–754

Not yet checked against the official Gazette; verify before relying on it.

Reproduced from the Gazette of India · verification status above

383. Procedure for Hydraulic Test.─(1)Every economiser for registration shall be hydraulically tested in the presence of Inspector to 1½ times the maximum allowable working pressure. Hydraulic tests of economisers at subsequent examination when required by the Competent Person, shall be made after the inspection.

(2)The test pressure to be applied to economisers at subsequent examinations shall be from 1.25 to 1.5 times the maximum allowable working pressure of the economisers. During the test, all parts externally and in the flues shall be noted for leakage.

Calculator (on SteamCalc, a separate free site · calculation aid, engineering review pending)

Hydraulic test pressure (regulations 167, 298, 383)

Independent explanation — not the law · draft · engineer review in progress

In short

Regulation 383 sets the hydraulic test pressures for economisers.

Key points

  • (1) For registration, every economiser is tested in the Inspector's presence to 1½ times the maximum allowable working pressure.
  • (1) At subsequent examinations, a hydraulic test is made only when the Competent Person requires it, and after the inspection.
  • (2) The subsequent test pressure is from 1.25 to 1.5 times the maximum allowable working pressure. All parts, externally and in the flues, are checked for leakage during the test.

Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.

Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).

Orientation hints (unverified)

These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.

Historical 1950-edition reg.Heading as OCR'dHeading similaritySource image
56Hydraulic Test100%Chapter II (DPIIT scan), image 10
72Hydraulic Test100%Chapter II (DPIIT scan), image 14
527Procedure for Hydraulic test100%Chapter XI (DPIIT scan), image 8

Amendment history of the candidate IBR 1950 regulations: Reg. 56 (3 amendments) · Reg. 527 (1 amendment)

IBR 1950 regulation 56 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 56 page for its amendments.

Reg. 56
MATERIALS OF CONSTRUCTION

SEAMLESS FERRITIC PIPES FOR HIGH TEMPERATURE SERVICE

 Hydraulic Test

(i) Each pipe shall be tested by the manufacturer and shall withstand a hydraulic pressure to one and half times the design pressure but not greater than pressure calculated by the following formula given below.  In the absence of working pressure is indicated in the Test Certificate then the tested pressure indicated in the Test Certificate divided by 1.5 shall be the maximum working pressure 

P = 2 S t / d                          

where     P = test pressure

                D = specified outside diameter of the pipe

                t = specified wall thickness of the pipe

S = stress which shall be taken as 40% of the minimum tensile strength at room temperature.

(ii)  Notwithstanding anything contained in the above clause, the hydraulic test at the maker's works may be dispensed with provided that the pipes are subject to non destructive testing by an appropriate method like Ultrasonic or Eddy current or stray flux testing

IBR 1950 regulation 527 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 527 page for its amendments.


Reg. 526
, Reg. 527, Reg. 528
STANDARD CONDITIONS FOR THE DESIGN AND CONSTRUCTION OF ECONOMIZER, FEED PIPES, FEED HEATERS AND OTHER SIMILAR VESSELS

REGULATIONS FOR REGISTRATION AND INSPECTION OF ECONOMISERS AND FEED PIPES

Procedure at subsequent inspection
a)

After the economiser has been cleaned the Inspector shall make a thorough examination so far as its construction permits. The external condition of the tubes should be carefully noted for wasting especially at the feed inlet end and all accessible tubes should be calibered. The internal surfaces of cast iron tubes should be closely observed for graphitic wasting as far as it is possible and in the event of any tube failure these should be broken up for scrutiny so that the general internal condition of the other tubes may be estimated.

b) Where tubes or other parts are wasted, the strength should be recalculated.
c) The scraper gear should be examined to note if any parts are missing if the length of travel is adequate and if the scrapers are correctly adjusted.
d) All cap bolts are to be inspected, also the condition and position of the dampers and baffles.
e) The record of each inspection and calculations will be entered in the Memorandum of Inspection Book.


Reg. 527

STANDARD CONDITIONS FOR THE DESIGN AND CONSTRUCTION OF ECONOMIZER, FEED PIPES, FEED HEATERS AND OTHER SIMILAR VESSELS

REGULATIONS FOR REGISTRATION AND INSPECTION OF ECONOMISERS AND FEED PIPES

Procedure for Hydraulic test

Every economiser for registration shall be hydraulically tested in the presence of an Inspector to 1 ½ times the working pressure. Hydraulic tests of economisers at subsequent examinations shall when required by the Inspector, be made after the inspection. The test pressure to be applied to economisers at subsequent examinations shall be from 1-1/4  to 1-1/2 times the working pressure of the economisers. During the test, all parts externally and in the flues shall be noted for leakage.


Reg. 528

STANDARD CONDITIONS FOR THE DESIGN AND CONSTRUCTION OF ECONOMIZER, FEED PIPES, FEED HEATERS AND OTHER SIMILAR VESSELS

REGULATIONS FOR REGISTRATION AND INSPECTION OF ECONOMISERS AND FEED PIPES

Memorandum of Inspection Book

In this book the Inspector shall enter all particulars and dimensions of the economiser with the required calculations for the various parts together with details of hydraulic test. At subsequent inspection the Inspector shall enter all notes pertaining to the condition of the various parts.

Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.

Instrument
Indian Boiler Regulations, 2026 (made by the Central Boilers Board under s.40 of the Boilers Act, 2025)
Notification
F.No. P-30014/3/2021-Boiler dated 7 Aug 2026
Published
Gazette of India, Extraordinary, Part III Sec. 4, No. 596, 1 Oct 2026 (CG-DL-E-06102026-276813)
In force
1 Oct 2026 (reg. 1(3): date of publication in the Official Gazette)
Printed Gazette page
753–754
PDF page index
753–754 · open official e-Gazette PDF
Extraction
pdftotext layout mode, sequential regulation detector · text hash 5eb10021add2a81b
Verification
Official text — not yet verified
Amendments checked
None known after 1 Oct 2026 as of build date (not a guarantee). Amendment log
How to cite

Indian Boiler Regulations, 2026, reg. 383, Regulation 383, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.753–754. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).

The citation refers to the government publication. Cite the Gazette, not this website.

Help improve this page

Engineers like you keep IBRsource accurate. Every checked correction or tip helps the next reader.