Indian Boiler Regulations, 2026 · Chapter 11 · Standard Conditions for the Design and Construction of Economisers, Feed Pipes, Feed Heaters and Other Similar Vessels
Regulation 383. Procedure for Hydraulic Test
Not yet checked against the official Gazette; verify before relying on it.
383. Procedure for Hydraulic Test.─(1)Every economiser for registration shall be hydraulically tested in the presence of Inspector to 1½ times the maximum allowable working pressure. Hydraulic tests of economisers at subsequent examination when required by the Competent Person, shall be made after the inspection.
(2)The test pressure to be applied to economisers at subsequent examinations shall be from 1.25 to 1.5 times the maximum allowable working pressure of the economisers. During the test, all parts externally and in the flues shall be noted for leakage.
In short
Regulation 383 sets the hydraulic test pressures for economisers.
Key points
- (1) For registration, every economiser is tested in the Inspector's presence to 1½ times the maximum allowable working pressure.
- (1) At subsequent examinations, a hydraulic test is made only when the Competent Person requires it, and after the inspection.
- (2) The subsequent test pressure is from 1.25 to 1.5 times the maximum allowable working pressure. All parts, externally and in the flues, are checked for leakage during the test.
Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.
Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).
Orientation hints (unverified)
These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.
| Historical 1950-edition reg. | Heading as OCR'd | Heading similarity | Source image |
|---|---|---|---|
| 56 | Hydraulic Test | 100% | Chapter II (DPIIT scan), image 10 |
| 72 | Hydraulic Test | 100% | Chapter II (DPIIT scan), image 14 |
| 527 | Procedure for Hydraulic test | 100% | Chapter XI (DPIIT scan), image 8 |
Amendment history of the candidate IBR 1950 regulations: Reg. 56 (3 amendments) · Reg. 527 (1 amendment)
IBR 1950 regulation 56 as last published in the DPIIT web edition (archived 2022)
Unofficial archived copy, not verified; see the regulation 56 page for its amendments.
| Reg. 56 MATERIALS OF CONSTRUCTION SEAMLESS FERRITIC PIPES FOR HIGH TEMPERATURE SERVICE Hydraulic Test |
| (i) Each pipe shall be tested by the manufacturer and shall withstand a hydraulic pressure to one and half times the design pressure but not greater than pressure calculated by the following formula given below. In the absence of working pressure is indicated in the Test Certificate then the tested pressure indicated in the Test Certificate divided by 1.5 shall be the maximum working pressure P = 2 S t / d where P = test pressure D = specified outside diameter of the pipe t = specified wall thickness of the pipe S = stress which shall be taken as 40% of the minimum tensile strength at room temperature. (ii) Notwithstanding anything contained in the above clause, the hydraulic test at the maker's works may be dispensed with provided that the pipes are subject to non destructive testing by an appropriate method like Ultrasonic or Eddy current or stray flux testing |
IBR 1950 regulation 527 as last published in the DPIIT web edition (archived 2022)
Unofficial archived copy, not verified; see the regulation 527 page for its amendments.
|
REGULATIONS FOR REGISTRATION AND INSPECTION OF ECONOMISERS AND FEED PIPES | ||||||||||
| ||||||||||
|
REGULATIONS FOR REGISTRATION AND INSPECTION OF ECONOMISERS AND FEED PIPES | ||||||||||
| ||||||||||
|
REGULATIONS FOR REGISTRATION AND INSPECTION OF ECONOMISERS AND FEED PIPES | ||||||||||
|
Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.


Indian Boiler Regulations, 2026, reg. 383, Regulation 383, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.753–754. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).
The citation refers to the government publication. Cite the Gazette, not this website.