Indian Boiler Regulations, 2026 · Chapter 11 · Standard Conditions for the Design and Construction of Economisers, Feed Pipes, Feed Heaters and Other Similar Vessels

Regulation 384. Memorandum of Inspection Book

Official text — not yet verifiedGazette 1 Oct 2026 · printed p. 754

Not yet checked against the official Gazette; verify before relying on it.

Reproduced from the Gazette of India · verification status above

384. Memorandum of Inspection Book .─ (1) A Memorandum of Inspection Book shall be prepared for each economiser in Form-XVIII and the Inspector shall enter all particulars in ink and dimensions of the economisers with the particulars of hydraulic test and his inspection notes in this book;

(2)At subsequent inspection, Competent Person shall enter the dates of the Inspections, hydraulic tests when such are made with their notes pertaining to the condition of the various parts;

(3)the Inspector or Competent Person, as the case may be, shall also enter in the Memorandum of Inspection Book, the general condition of the economiser and of repairs;

(4)(a) On submission of the Memorandum Book to the Chief Inspector, he will in the case of newly registered economisers, check all particulars and calculations and approve the design pressure that is to be permitted.

(b)In the case of old economisers, the Chief Inspector shall examine the Inspector’s notes of inspection and proposals made for repairs.

(c)A pressure once approved for the economiser shall not be altered without the written authority of the Chief Inspector.

(d)The Memorandum of Inspection Book shall be kept clean and up-to-date and the Inspection Book except when actually required by the Competent Person, shall be kept in the office of the Chief Inspector.

Referenced provisions

Form-XVIII

Independent explanation — not the law · draft · engineer review in progress

In short

Regulation 384 covers the Memorandum of Inspection Book (Form-XVIII) kept for each economiser: who writes in it and how the Chief Inspector uses it.

Key points

  • (1) The Inspector enters, in ink, all particulars and dimensions, the hydraulic test details and inspection notes.
  • (2) At subsequent inspections, the Competent Person enters inspection and hydraulic test dates and notes on the condition of parts.
  • (3) The Inspector or Competent Person also records the general condition of the economiser and any repairs.
  • (4)(a) For a newly registered economiser, the Chief Inspector checks all particulars and calculations and approves the design pressure.
  • (4)(b) For old economisers, the Chief Inspector examines the inspection notes and repair proposals.
  • (4)(d) The book is kept clean and up to date, and stays in the Chief Inspector's office except when the Competent Person actually needs it.

Watch out

  • (4)(c) Once approved, the pressure cannot be altered without the Chief Inspector's written authority.

Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.

Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).

Orientation hints (unverified)

These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.

Historical 1950-edition reg.Heading as OCR'dHeading similaritySource image
528Memorandum of Inspection Book100%Chapter XI (DPIIT scan), image 8

Amendment history of the candidate IBR 1950 regulation: Reg. 528 (1 amendment)

IBR 1950 regulation 528 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 528 page for its amendments.


Reg. 526
, Reg. 527, Reg. 528
STANDARD CONDITIONS FOR THE DESIGN AND CONSTRUCTION OF ECONOMIZER, FEED PIPES, FEED HEATERS AND OTHER SIMILAR VESSELS

REGULATIONS FOR REGISTRATION AND INSPECTION OF ECONOMISERS AND FEED PIPES

Procedure at subsequent inspection
a)

After the economiser has been cleaned the Inspector shall make a thorough examination so far as its construction permits. The external condition of the tubes should be carefully noted for wasting especially at the feed inlet end and all accessible tubes should be calibered. The internal surfaces of cast iron tubes should be closely observed for graphitic wasting as far as it is possible and in the event of any tube failure these should be broken up for scrutiny so that the general internal condition of the other tubes may be estimated.

b) Where tubes or other parts are wasted, the strength should be recalculated.
c) The scraper gear should be examined to note if any parts are missing if the length of travel is adequate and if the scrapers are correctly adjusted.
d) All cap bolts are to be inspected, also the condition and position of the dampers and baffles.
e) The record of each inspection and calculations will be entered in the Memorandum of Inspection Book.


Reg. 527

STANDARD CONDITIONS FOR THE DESIGN AND CONSTRUCTION OF ECONOMIZER, FEED PIPES, FEED HEATERS AND OTHER SIMILAR VESSELS

REGULATIONS FOR REGISTRATION AND INSPECTION OF ECONOMISERS AND FEED PIPES

Procedure for Hydraulic test

Every economiser for registration shall be hydraulically tested in the presence of an Inspector to 1 ½ times the working pressure. Hydraulic tests of economisers at subsequent examinations shall when required by the Inspector, be made after the inspection. The test pressure to be applied to economisers at subsequent examinations shall be from 1-1/4  to 1-1/2 times the working pressure of the economisers. During the test, all parts externally and in the flues shall be noted for leakage.


Reg. 528

STANDARD CONDITIONS FOR THE DESIGN AND CONSTRUCTION OF ECONOMIZER, FEED PIPES, FEED HEATERS AND OTHER SIMILAR VESSELS

REGULATIONS FOR REGISTRATION AND INSPECTION OF ECONOMISERS AND FEED PIPES

Memorandum of Inspection Book

In this book the Inspector shall enter all particulars and dimensions of the economiser with the required calculations for the various parts together with details of hydraulic test. At subsequent inspection the Inspector shall enter all notes pertaining to the condition of the various parts.

Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.

Instrument
Indian Boiler Regulations, 2026 (made by the Central Boilers Board under s.40 of the Boilers Act, 2025)
Notification
F.No. P-30014/3/2021-Boiler dated 7 Aug 2026
Published
Gazette of India, Extraordinary, Part III Sec. 4, No. 596, 1 Oct 2026 (CG-DL-E-06102026-276813)
In force
1 Oct 2026 (reg. 1(3): date of publication in the Official Gazette)
Printed Gazette page
754
PDF page index
754 · open official e-Gazette PDF
Extraction
pdftotext layout mode, sequential regulation detector · text hash 11ebdd97043f8aaf
Verification
Official text — not yet verified
Amendments checked
None known after 1 Oct 2026 as of build date (not a guarantee). Amendment log
How to cite

Indian Boiler Regulations, 2026, reg. 384, Regulation 384, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.754. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).

The citation refers to the government publication. Cite the Gazette, not this website.

Help improve this page

Engineers like you keep IBRsource accurate. Every checked correction or tip helps the next reader.