Regulation 375. Bolts, studs joints and Flanges

Official text — not yet verifiedGazette 1 Oct 2026 · printed pp. 748–749Formula / symbols

Not yet checked against the official Gazette; verify before relying on it.

Reproduced from the Gazette of India · verification status above

375. Bolts, studs joints and Flanges.─ (1) The maximum allowable working pressure for the bolts shall as per the following formula, ─

                            2

      N x C      1.28

P  =  ------- D - --------            Equation (11/1)

      A          n

Where,
N = No. of bolts securing the parts,
n = No. of screws threads per inch,
D = Bolt diameter in inches measured over the threads,
A = The area exposed to pressure which is assumed to be bounded by a line midway between the pitch line of the bolts and the inner edge of the flange where flat joints are used with joints rings. Where conical joints faces are used with joint rings, of curvilinear cross-section, the area exposed to pressure shall be assumed to extend to the root of the thread where the tube ends are screwed, or to a corresponding boundary if the flanges are attached by other means. C = 4,700 for steel bolts or studs of 28 tons/sq.in. minimum ultimate tensile stress where the diameter over thread is less than 3/4 inch,
C = 5,100 for steel bolts or studs of 30 tons /sq. in. minimum ultimate tensile stress where the diameter over thread is less than 3/4 inch.

C = 5,600 for steel bolts or studs of 35 tons /sq. in. minimum ultimate tensile stress where the diameter over thread is less than 3/4 inch.

C = 5,600 for steel bolts or studs of 28 tons/sq. in. minimum ultimate tensile stress where the diameter over thread is not less than 3/4 inch and not greater than 7/8 inch.

C = 7,000 for steel bolts or studs of 28 tons/sq. in. minimum ultimate tensile stress where the diameter over thread is greater than 7/8 inch.

Where the bolts or studs used have a tensile strength exceeding 32 tons sq. in., a plate shall be permanently fixed to the economiser structure in a prominent position drawing attention to this fact in case replacements of bolts or studs are necessary. In no case shall the nuts be exposed to the action of the flue gases.

(2)The thickness of each flange shall be not less than that given by the following equation:

          t =      [P.D. (D1 - D)]                       Equation (11/2)
Where,             ------------------

                             2

t = Thickness of flange in thirty-seconds of an inch.

P = Maximum Allowable Working pressure, in lbs. per square inch (gauge)

D = Outside diameter of the tube in inches.

D1 = Pitch circle diameter or bolts or studs in inches.

Provided that such flange is cast integral with the body and with the appropriate internal corner radius. In no case, however, the thickness of a flange shall be less than 24 thirty -seconds of an inch.

Parts of this extracted text look garbled; read the Gazette page before using any value.

Tables and formulae are shown in their extracted layout. Alignment, superscripts and subscripts may be lost. The Gazette page image is authoritative.

Independent explanation — not the law · draft · engineer review in progress

In short

Regulation 375 gives the formulae for the maximum allowable working pressure of economiser joint bolts and studs, and for the minimum flange thickness. Both use inch-based units.

Key points

  • (1) Equation (11/1) gives the pressure P from N (number of bolts), n (screw threads per inch), D (bolt diameter over the threads, in inches), A (area exposed to pressure) and a constant C.
  • The text defines how A is bounded for flat joints with joint rings and for conical joint faces with curvilinear rings.
  • C depends on the bolt or stud's minimum ultimate tensile stress and its diameter over the thread. Take the values from the Official text tab.
  • (2) Equation (11/2) gives the flange thickness t in thirty-seconds of an inch, from P (in lbs. per square inch gauge), D (tube outside diameter) and D1 (pitch circle diameter of the bolts or studs).

Watch out

  • Where bolts or studs have a tensile strength exceeding 32 tons per sq. in., a plate must be permanently fixed in a prominent position on the economiser structure to draw attention to this when bolts or studs are replaced.
  • Nuts must never be exposed to the flue gases.
  • The flange equation applies where the flange is cast integral with the body with the appropriate internal corner radius. No flange may be thinner than 24 thirty-seconds of an inch.
  • Both equations are garbled in the extracted text. Check the Gazette page for their exact form.

Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.

Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).

Orientation hints (unverified)

These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.

Historical 1950-edition reg.Heading as OCR'dHeading similaritySource image
208Bolts and Studs100%Chapter IV (DPIIT scan), image 8
410Flanges100%Chapter X (DPIIT scan), image 4
IBR 1950 regulation 208 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 208 page for its amendments.

Reg. 208
STAYS

Bolts and Studs

a) Bolts and studs connecting parts by boilers such as shell, end plates, tube plates, furnaces, up takes, externally fitted manhole covers, mountings, etc. may be made either of steel or good quality wrought iron.
b) The maximum working pressure for the bolts or studs shall be calculated by the following formula: -
W. P. =

N x C

( D - 1.28 )2 Eqn.(45)
A n

where
D is the diameter of bolt or stud over threads in inches

N is the number of bolts or studs securing the part,

n is the number of threads of screws per inch,

C = 4,700 for steel bolts or studs of 28 tons/sq. in. minimum ultimate tensile stress where the diameter over thread is less than 3/4 inch,

C = 5,100 for steel bolts or studs of 30 tons/sq. in. minimum ultimate tensile stress where the diameter over thread is less than 3/4 inch

C = 5,600 for steel bolts or studs of 35 tons/sq. in minimum ultimate tensile stress where the diameter over thread is less than 3/4 inch.

C = 5,600 for steel bolts or studs of 28 tons/sq. in minimum ultimate tensile stress where the diameter over thread is not less than 3/4 inch and not greater than 7/8 inch.

C = 7,000 for steel bolts for studs of 28 tons/sq. in minimum ultimate tensile stress where the diameter over thread is greater than 7/8 inch.

When the material is iron, a reduction, of 15 per cent shall be made in the working pressure as calculated by the formula.

A is the area in square inches of the surface supported by the bolts or studs. For jointed flanges the area shall be taken to extend to midway between the pitch line of the bolts and the inner edge of the flange by which the part is secured.
IBR 1950 regulation 410 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 410 page for its amendments.

Reg. 410, Reg. 411, Reg. 412
RIVETED STEEL BOILERS

Flange-Thickness and Drilling

The thickness and drilling of flanges of standpipes shall be in accordance with the Appendix (E).



Reg. 411
RIVETED STEEL BOILERS

Pads

These shall comply with Regulation 155.



Reg. 412
RIVETED STEEL BOILERS

Unstayed Flat-End Plates

The working pressure of unstayed flat-end plates shall be determined by the following formula:

W.P. = 2S(t-2)² Eqn. (98)
D²

Where,

t = thickness of plate in thirty-seconds of an inch.
W.P. = Working pressure in pounds per square inch.
D = Diameter in inches of the pitch circle of the bolts or rivets when the plate is attached to an outside flange or the internal diameter of the shell when the plate is attached to an inside flange.
S = Minimum tensile stress of the plate in tons per square inch.

In no case shell the thickness of an unstayed flat-end plate be less than 3/8 inch.

Where an unstayed flat-end plate is pierced for electrodes or other fittings by openings having a diameter not greater than 2 ½ inches and the pitch of the openings in inches is not less than four times the diameter of the openings in inches, compensation is not required.

Where the diameter of the openings in an unstayed flat-end plate is greater than 2 ½ inches or the pitch in inches is less than four times the diameter of the openings, adequate compensation shall be provided in the manner described in Regulations 170, 171 and 186.

Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.

Instrument
Indian Boiler Regulations, 2026 (made by the Central Boilers Board under s.40 of the Boilers Act, 2025)
Notification
F.No. P-30014/3/2021-Boiler dated 7 Aug 2026
Published
Gazette of India, Extraordinary, Part III Sec. 4, No. 596, 1 Oct 2026 (CG-DL-E-06102026-276813)
In force
1 Oct 2026 (reg. 1(3): date of publication in the Official Gazette)
Printed Gazette page
748–749
PDF page index
748–749 · open official e-Gazette PDF
Extraction
pdftotext layout mode, sequential regulation detector · text hash f0ceee92e9288f40
Verification
Official text — not yet verified
Amendments checked
None known after 1 Oct 2026 as of build date (not a guarantee). Amendment log
How to cite

Indian Boiler Regulations, 2026, reg. 375, Regulation 375, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.748–749. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).

The citation refers to the government publication. Cite the Gazette, not this website.

Help improve this page

Engineers like you keep IBRsource accurate. Every checked correction or tip helps the next reader.