Indian Boiler Regulations, 2026 · Chapter 11 · Standard Conditions for the Design and Construction of Economisers, Feed Pipes, Feed Heaters and Other Similar Vessels
Regulation 380. Preparation for inspection
Not yet checked against the official Gazette; verify before relying on it.
380. Preparation for inspection.─ (1) (a) At each inspection, the economiser shall be emptied and thoroughly cleaned internally and externally and in the flues.
(b)All mountings shall be opened up and all caps, doors and blank flanges removed to permit adequate inspection.
(2)The owner of an economiser to which this regulation is applicable shall obtain the approval of the chief inspector in writing to the method of disconnection which he proposes to use and shall be responsible for ensuring that the method so approved is followed in practice.
In short
Regulation 380 sets how an economiser must be prepared before each inspection.
Key points
- (1)(a) Empty the economiser and clean it thoroughly inside, outside and in the flues.
- (1)(b) Open up all mountings and remove all caps, doors and blank flanges so it can be properly inspected.
- (2) The owner must get the Chief Inspector's written approval of the method of disconnection to be used, and is responsible for making sure that approved method is followed.
Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.
Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).
Orientation hints (unverified)
These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.
| Historical 1950-edition reg. | Heading as OCR'd | Heading similarity | Source image |
|---|---|---|---|
| 524 | Preparation for inspection | 100% | Chapter XI (DPIIT scan), image 7 |
IBR 1950 regulation 524 as last published in the DPIIT web edition (archived 2022)
Unofficial archived copy, not verified; see the regulation 524 page for its amendments.
| Reg. 524, Reg. 525 REGULATIONS FOR REGISTRATION AND INSPECTION OF ECONOMISERS AND FEED PIPES | |||||||||||||||||||
| |||||||||||||||||||
|
REGULATIONS FOR REGISTRATION AND INSPECTION OF ECONOMISERS AND FEED PIPES | |||||||||||||||||||
|
| Next >>> |
Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.

Indian Boiler Regulations, 2026, reg. 380, Regulation 380, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.751. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).
The citation refers to the government publication. Cite the Gazette, not this website.