Indian Boiler Regulations, 2026 · Chapter 11 · Standard Conditions for the Design and Construction of Economisers, Feed Pipes, Feed Heaters and Other Similar Vessels
Regulation 388. Casual visits
Not yet checked against the official Gazette; verify before relying on it.
388. Casual visits.─ (1) The Inspector shall note that the economiser is working satisfactorily, the relief valves are correctly adjusted, the scraper gear is operating and the external brick work is free from cracks.
(2)He shall also ascertain that the maker’s instructions for working are being strictly followed by the owner.
Note: It is recommended that the feed inlet temperature to the economiser shall not be less than 38°C, to prevent sweating and consequent external corrosion of the tube and bottom headers.
In short
Regulation 388 lists what an Inspector checks on a casual visit to an economiser.
Key points
- (1) The economiser is working satisfactorily, the relief valves are correctly adjusted, the scraper gear is operating and the external brickwork is free from cracks.
- (2) The owner is strictly following the maker's instructions for working.
Watch out
- Note: the feed inlet temperature is recommended to be not less than 38°C, to prevent sweating and external corrosion of the tubes and bottom headers. This is a recommendation in the note, not a numbered requirement.
Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.
Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).
Orientation hints (unverified)
These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.
| Historical 1950-edition reg. | Heading as OCR'd | Heading similarity | Source image |
|---|---|---|---|
| 531 | Casual yisits | 92% | Chapter XI (DPIIT scan), image 9 |
IBR 1950 regulation 531 as last published in the DPIIT web edition (archived 2022)
Unofficial archived copy, not verified; see the regulation 531 page for its amendments.
|
REGULATIONS FOR REGISTRATION AND INSPECTION OF ECONOMISERS AND FEED PIPES | |||||
| |||||
|
REGULATIONS FOR REGISTRATION AND INSPECTION OF ECONOMISERS AND FEED PIPES | |||||
| |||||
|
REGULATIONS FOR REGISTRATION AND INSPECTION OF ECONOMISERS AND FEED PIPES | |||||
| |||||
|
REGULATIONS FOR REGISTRATION AND INSPECTION OF ECONOMISERS AND FEED PIPES | |||||
| |||||
Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.


Indian Boiler Regulations, 2026, reg. 388, Regulation 388, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.754–755. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).
The citation refers to the government publication. Cite the Gazette, not this website.