Regulation 456. Horizontal shelves of tube plates forming part of the Shell

Official text — not yet verifiedGazette 1 Oct 2026 · printed p. 773Figure referencedFormula / symbols

Not yet checked against the official Gazette; verify before relying on it.

Reproduced from the Gazette of India · verification status above

456.Horizontal shelves of tube plates forming part of the Shell.─(1)The number of gusset required to support the horizontal shelves of tube plates to withstand vertical load due to the pressure on the boiler end shall be determined in the following manner:

(a)For combustion chamber tube plates, the minimum number of the gussets shall be:-

Where C exceeds 45601 gusset.
Where C exceeds 62402 gussets.
Where C exceeds 74403 gussets.

Columns reconstructed from the extracted text; check against the Gazette page.

Show original extracted text (diagnostic, not authoritative)
Where C exceeds 4560                                  1 gusset.
Where C exceeds 6240                                  2 gussets.

Where C exceeds 7440                                  3 gussets.

(b)For smoke fox tube plate, the minimum number of gussets shall be:-

Where C exceeds 45601 gusset.
Where C exceeds 8400PAD2 gussets.
And C =---
t
Equation. (12/4)

Columns reconstructed from the extracted text; check against the Gazette page.

Show original extracted text (diagnostic, not authoritative)
Where C exceeds 4560                                  1 gusset.
Where C exceeds 8400                                  2 gussets.

                                                 PAD

                      And C =                    ---                                 Equation. (12/4)

                                                 t

Where,

A = is maximum horizontal dimension of the shell from the inside of the shell plate is to the outside of the tube plate in inches (See Figure 12/75),

D = is inside diameter of the boiler in inches,

P = is Maximum Allowable working pressure in pounds per square inch, t = is thickness of tube plate in thirty-seconds of an inch.

(2)The shell plates to which the sides of the tube plates are connected shall be not less than 1.5 mm thicker than is required by the formula applicable to shell plates with continuous circularity; and where gussets or other stays are not fitted to the shelves, the strength of the parts of the circumferential seams at the top and bottom of these plates from the outside of one tube plate to the outside of the other, shall be sufficient to with-stand the whole load on the boiler end, with a factor of safety of not less than 4.5.

Tables and formulae are shown in their extracted layout. Alignment, superscripts and subscripts may be lost. The Gazette page image is authoritative.

Figures cited in this regulation (1, exact crops of the Gazette)

Gazette Fig. 12/75
Fig. 12/75(no caption printed with this figure)
View Gazette page 817 · figure catalogue
Auto-traced outline: SVG · DXF (not to scale, may copy print defects)
Independent explanation — not the law · draft · engineer review in progress

In short

Sets the minimum number of gussets supporting horizontal shelves of tube plates that form part of the shell, and the related shell plate rule.

Key points

  • (1) The number of gussets depends on the factor C from Equation (12/4), which uses A (horizontal dimension from inside of shell plate to outside of tube plate, inches; Figure 12/75), D (inside diameter, inches), P (pressure, pounds per square inch) and t (tube plate thickness in thirty-seconds of an inch).
  • (1)(a) Combustion chamber tube plates: 1 gusset where C exceeds 4560, 2 where C exceeds 6240, 3 where C exceeds 7440 (apply the highest number that applies).
  • (1)(b) Smoke box tube plates: 1 gusset where C exceeds 4560, 2 where C exceeds 8400.
  • (2) The shell plates joined to the sides of the tube plates must be at least 1.5 mm thicker than the formula for a fully circular shell requires.
  • (2) Where no gussets or other stays are fitted to the shelves, the circumferential seams at top and bottom of these plates, from the outside of one tube plate to the outside of the other, must carry the whole load on the boiler end with a factor of safety of at least 4.5.

Watch out

  • Equation (12/4) uses inch and pound units, unlike most of this chapter.

Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.

Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).

Orientation hints (unverified)

These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.

Historical 1950-edition reg.Heading as OCR'dHeading similaritySource image
33Plates100%Chapter II (DPIIT scan), image 3
118Tube Plates100%Chapter III (DPIIT scan), image 2
634Tube plates100%Chapter XV (DPIIT scan), image 3
IBR 1950 regulation 33 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 33 page for its amendments.

Reg. 33
MATERIALS OF CONSTRUCTION

COPPER PLATES, STAY AND RIVET BARS

Plates

(a) Process.- The copper shall be fire-refined or electrolytic and hot-rolled from suitable cakes.

(b) Chemical Composition.- The chemical composition of the plates shall be as follows:-

Per cent.
Copper 99.2 minimum
Arsenic .30 to .50
Antimony 0.05 maximum
Bismuth 0.05 maximum
Oxygen 0.10 maximum

(c) Freedom from defects.- The plates shall be clean, smooth and free from defects and shall have a workmanlike finish. They shall be thoroughly annealed.

(d) Rolling Margin.- No plate shall be under the specified thickness at any part, not more than 5% over the calculated weight. The scrap margin, partly sheared and left attached, shall be not less than 3 inches at the ends and 1½ inches at each side.

(e) Tensile Tests.- One tensile test shall be taken from each plate as rolled.

The tensile breaking strength, from Standard Test Piece A, shall not be less than 14 tons per sq. inch with an elongation of not less than 35%.

(f) Hot and Cold Bend tests.- One hot (temperature between 1200°F and 1400°F) and one cold bend test shall be taken from each plate as rolled.

For either hot or cold bend tests, the test piece shall withstand being doubled over without fracture until the sides are touching and parallel.

IBR 1950 regulation 118 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 118 page for its amendments.

Reg. 118, Reg. 119, Reg. 120
END PLATES

 

Tube Plates

Smoke-box tube plates shall be flanged for attachment to the barrel or shall be flat and connected thereto by an external riveted angle ring.

Reg. 119
END PLATES

 

Parts of flat tube plates within the tube nests

a) where the total area of all tube nests in directly fired multi-tubular boilers exceeds 7 sq. ft., stay tubes shall be fitted.

Where the total number of tubes in horizontal multitubular waste heat boilers and direct fired loco type boilers is arranged in one next, the area of which exceed 21 sq. ft., stay tubes shall be fitted.

In all cases where the total number of tubes is arranged in more than one nest, stay tubes shall be fitted.
b) The parts of tube plates which lie outside the nests of tubes shall be stayed or supported wherever the size of the area of plate subject to steam pressure necessitates staying or support, either by marginal stay tubes or other means.


Reg. 120
END PLATES
Flanging of End Plates

All flanges shall be a good fit to the shell and flues. Flogging and/or hammering in the fitting of these parts is prohibited. The caulking edges of all flanged plates shall be machined or machine gas cut.

Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.

Instrument
Indian Boiler Regulations, 2026 (made by the Central Boilers Board under s.40 of the Boilers Act, 2025)
Notification
F.No. P-30014/3/2021-Boiler dated 7 Aug 2026
Published
Gazette of India, Extraordinary, Part III Sec. 4, No. 596, 1 Oct 2026 (CG-DL-E-06102026-276813)
In force
1 Oct 2026 (reg. 1(3): date of publication in the Official Gazette)
Printed Gazette page
773
PDF page index
773 · open official e-Gazette PDF
Extraction
pdftotext layout mode, sequential regulation detector · text hash e78b9a513eeb95e5
Verification
Official text — not yet verified
Amendments checked
None known after 1 Oct 2026 as of build date (not a guarantee). Amendment log
How to cite

Indian Boiler Regulations, 2026, reg. 456, Regulation 456, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.773. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).

The citation refers to the government publication. Cite the Gazette, not this website.

Help improve this page

Engineers like you keep IBRsource accurate. Every checked correction or tip helps the next reader.