Regulation 592 — SHELL TYPE BOILERS OF WELDED CONSTRUCTION

Unofficial DPIIT web edition · not verified6 amendments found

Text in the DPIIT web edition

Archived copy captured 03 Aug 2022 (Wayback Machine). The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.

Unofficial DPIIT web edition · archived 2022 · not checked against the Gazette

Reg. 592

Furnaces, furnaces components, wet back reversal chambers and fire boxes of cylindrical form subject to external pressure.-

Furnaces:

a) Maximum furnace diameter. The mean diameter of furnaces shall not exceed 1800 mm.
b) Notations:

b - is the pitch of the furnace corrugations (in mm);

c - is the corrosion allowance = 0.75mm

d - is the mean diameter of furnace (in mm) (see note 1);

dmax - is the maximum mean diameter of the furnace (in mm)

dmin - is the minimum mean diameter of the furnace (in mm);

e - is the furnace plate thickness (in mm);
E - is Young’s modulus of elasticity (in kg/cm²) at the design temperature.
Et - is the specified minimum elevated temperature yield stress or the 0.2% proof stress at the design temperature (in kg/cm²);
F - is the cross-sectional area of a longitudinal section of the corrugated furnace wall, of length b and thickness (e-c) (in mm²) (see Figs. XII/94A to C, XII/94D to E, XII/94F to G).

I - is the second moment of area of one complete corrugation about its neutral axis excluding the corrosion allowance (in mm4);
Is - is the second moment of area of plain stiffener section(see Fig. XII/21 & XII/22) about its neutral axis, including a length of the furnace of 0.55 (de)1/2 on each side of the stiffener (in mm4) (see note 2);
L - is the distance between the centre of two effective points of support (in mm) (see note 3);
P - Is the design pressure (in kg/cm²)
S1 - is the factor of safety:
     =2.5 for furnaces in class I and class II boilers
    =3.5 for furnaces in class III boilers
    =2.0 for furnaces and wrapper plates not exposed to flame.
S2 - is the factor of safety:
    =3.0 for class I and class II boilers
    =3.9 for class III boilers
u - is the percentage out of roundness to be taken as 1.5 for plain furnaces      and1.0 for corrugated furnaces;
w - is the depth of corrugation (in mm).

NOTE 1: For corrugated furnaces, mean diameter is equal to inside diameter plus full depth of one corrugation referred to in Fig. XII/94  which is equal to the inside diameter + e + W.

NOTE 2: When calculating Is, it is only necessary to take into account a corrosion allowance on the furnace gas side.

NOTE 3: Stiffeners complying with figure XII/21 and XII/22 boiler and reversal chamber end plates are considered to be effective points of support.

NOTE 4: The design temperature of the furnace = ts +4e + 15 saturation temperature plus four times the thickness of the furnace plus 15.

Next >>>
Earlier text: the 2008 DIPP web edition

Furnaces, furnaces components, wet back reversal chambers and fire boxes of

cylindrical form subject to external pressure.-

Furnaces:

a)Maximum furnace diameter. The mean diameter of furnaces shall not exceed 1800 mm.

b)

Notations:

b - is the pitch of the furnace corrugations (in mm);

c - is the corrosion allowance = 0.75mm

d - is the mean diameter of furnace (in mm) (see note 1);

dmax - is the maximum mean diameter of the furnace (in mm)

dmin - is the minimum mean diameter of the furnace (in mm);

e - is the furnace plate thickness (in mm);

E - is Young’s modulus of elasticity (in kg/cm²) at the design temperature. Et - is the specified minimum elevated temperature yield stress or the 0.2% proof stress at the design temperature (in kg/cm²);

F - is the cross-sectional area of a longitudinal section of the corrugated furnace wall, of length b and thickness (e-c) (in mm²) (see Figs. XII/94A to C, XII/94D to E, XII/94F to G).

I - is the second moment of area of one complete corrugation about its neutral axis excluding the corrosion allowance (in mm⁴);

Is - is the second moment of area of plain stiffener section(see Fig. XII/21 & XII/22) about its neutral axis, including a length of the furnace of 0.55 (de)¹ᐟ² on each side of the stiffener (in mm⁴) (see note 2);

L - is the distance between the centre of two effective points of support (in mm) (see note 3);

P - Is the design pressure (in kg/cm²)

S1 - is the factor of safety: =2.5 for furnaces in class I and class II boilers =3.5 for furnaces in class III boilers =2.0 for furnaces and wrapper plates not exposed to flame.

S2 - is the factor of safety: =3.0 for class I and class II boilers =3.9 for class III boilers u - is the percentage out of roundness to be taken as 1.5 for plain furnaces and1.0 for corrugated furnaces; w - is the depth of corrugation (in mm).

NOTE 1: For corrugated furnaces, mean diameter is equal to inside diameter plus full depth of one corrugation referred to in Fig. XII/94 which is equal to the inside diameter + e + W.

NOTE 2: When CALCULATING Is, it is only necessary to take into account a corrosion allowance on the furnace gas side.

NOTE 3: Stiffeners complying with figure XII/21 and XII/22 boiler and reversal chamber end plates are considered to be effective points of support.

NOTE 4: The design temperature of the furnace = ts +4e + 15 saturation

temperature plus four times the thickness of the furnace plus 15.

Next >>>

Amendments found

Machine-assisted list from the amending notifications (DPIIT copies; 1990–1998 from scanned Gazette issues on India Code); may be incomplete.

DateNotificationPartActionWhat changed (summary)Web edition
1994-02-07G.S.R. 107 OCR of scan(d)SubstitutedReplaces the last sentence: depth of corrugation plus plate thickness shall not be less than 51 millimetres.listed before the capture
1996-12-06G.S.R. 59 OCR of scanSubstitutedReplaces regulation 592 on furnaces, furnace components, wet-back reversal chambers and fireboxes under external pressure, with design equations.listed before the capture
1996-12-06G.S.R. 59 OCR of scanfigures after XII/93InsertedInserts Figures XII/94 (corrugation section properties) and XII/95 (bowling hoops).listed before the capture
1997-04-29compilation-1987-1998#p74 OCR of compilationChangedErrata correcting notation and equations in the new regulation 592.listed before the capture
2001-12-10G.S.R. 672(j)(i)AmendedAdds at the end a formula for the design temperature of reversal chamber wrapper plates.listed before the capture
2015-08-26G.S.R. 664(E)(b)AmendedBases Et on the governing code of the material.listed before the capture

Possible IBR 2026 successors (heading match, unverified): Reg. 94, Reg. 95, Reg. 487, Reg. 488