Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)
Regulation 567 — Dished ends subject to internal pressure
Text in the DPIIT web edition
Archived copy captured 03 Aug 2022 (Wayback Machine); the same page also prints regulation 567A. The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.
| Reg. 567, Reg. 567A | ||||||||||||||||||||||
Reg. 567A
|
Earlier text: the 2008 DIPP web edition
Dished ends subject to internal pressure
a)For unstayed ends of shells and tops of vertical boilers and the like boiler parts, when dished to partial spherical form the maximum working pressure shall be determined by the following formula:-
15 x S X (t-1)
WP =
R Equation XII/7
WP is the working pressure in pounds per square inch.
t is thickness of the end plate in thirty seconds of an inch but in no case this shall be less than the thickness of the shell to which it is attached.
R is the inner radius of curvture of the end in inches, which shall not exceed the external diameter of the shell to which it is attached.
S is the minimum tensile breaking strength of plate in tons per square inch, or whatever is allowed for it.
b)The inside radius to which a crown plate is dished shall be not greater than the external diameter of the cylinder to which it is attached.
c)The inside radius of curvature of the flanges to the shell shall be not less than 4 times the thickness of the crown plate and in no case less than 2 ½ inches.
d)The inside radius of curvature of flanges to uptakes shall be not less than twice the thickness of the crown plate and in no case less than 1 inch.
e)When the end has a manhole in it (t-5), shall be substituted for (t -1) in the formula.
f)The total depth of flange of manhole from the outer surface in inches measured on the minor axis shall be at least equal to-
√T X W depth of flange in inches Equation XII/8
where T is the thickness of the plate in inches and W is the minor axis of the hole in inches.
g)The depth of the crown plate opening from the commencement of the curvature of the flanging radius shall be not less than twice the plate thickness with a minimum of one inch.
Possible IBR 2026 successors (heading match, unverified): Reg. 116, Reg. 122, Reg. 137, Reg. 178, Reg. 407, Reg. 421, Reg. 458, Reg. 460