Regulation 587 — Longitudinal Bar Stays
Text in the DPIIT web edition
Archived copy captured 03 Aug 2022 (Wayback Machine); the same page also prints regulation 588. The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.
| Reg. 587, Reg. 588 | |||||||||||||||||||||||||||||||||
Reg. 588 Loads on Stay Tubes and Bar Stays
| |||||||||||||||||||||||||||||||||
Earlier text: the 2008 DIPP web edition
Longitudinal Bar Stays
The maximum working pressure for longitudinal bar stays is to be calculated from the appropriate one of the following two formulae:
C 1.28
WP= (D - ------------)² Equation XII/21
A N
C x D1²
WP= Equation XII/22
A
WP is working pressure in pounds per square inch,
D is diameter of stays over threads in inches,
D1 is diameter of body of stays at its smallest part in inches,
N is the number of threads of stay per inch,
A is area in square inches supported by one stay.
C is values given in Table below:
TABLE XII/5
Stress on Longitudinal Bar Stays
Range of tensile strength of bar Value of C
Tons per square inch Pounds per square inch
26/30 7850
28/32 8640
30/34 9420
32/36 10200
Where bar stays are fitted in vertical boilers, not less than four bar stays shall be fitted to boilers of 4 feet and over but under 5 feet in diameter; five bar stays to boilers of 5 feet and over but under 6 feet in diameter; six bar stays to boiler of 6 feet and over in diameter.
In no case, shall the diameter of the stay at any part be less than 1 inch. Where joined stays are fitted, the strength of the knuckle joint employed shall be at least equal to the strength of the remainder of the bar stay.