Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)
Regulation 572 — Raised manhole frames, cover plates and joint bolts
Text in the DPIIT web edition
Archived copy captured 03 Aug 2022 (Wayback Machine); the same page also prints regulations 573, 574. The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.
| Reg. 572, Reg. 573, Reg. 574 | |||||||||||||||||||||||||
Reg. 573 Stand Pipes and branches-
Reg. 574 Stayed Flat surfaces (other than Crowns of Vertical Boilers). Stayed heads/ Braced and stayed surfaces.
| |||||||||||||||||||||||||
Earlier text: the 2008 DIPP web edition
Raised manhole frames, cover plates and joint bolts
Raised circular manhole frames not exceeding 16 inches in diameter shall not be less than ¾ inch thick in all parts.
The circular cover plates and joint flanges for such frames shall be not less than-
1 inch thick for pressures not exceeding 120 pounds per square inch.
1- 1/8 inches thick for pressures exceeding 120 pounds per square inch but not exceeding 200 pounds per square inch.
1 ¼ inches thick for pressure exceeding 200 pounds but not exceeding 250 pounds per square inch.
For pressure exceeding 250 pounds per square inch, raised circular manhole frames shall not be fitted.
The cover plates shall be secured by at least sixteen steel bolts not less than 1 inch diameter, such that the stress in the bolts due to steam pressure shall not exceed:5,000 pounds per square inch for 1 inch bolts. 6,000 pounds per square inch for 1- 1/8 inches bolts. 6,500 pounds per square inch for 1 ¼ inches bolts.
For the purpose of calculation the pressure shall be assumed to act on the whole area within the pitch circle of the bolts and the bolt area at the bottom of the screw thread shall be taken.
Possible IBR 2026 successors (heading match, unverified): Reg. 134, Reg. 138, Reg. 429, Reg. 464, Reg. 571