Indian Boiler Regulations, 2026 · Chapter 3 · Construction and Workmanship

Regulation 89. Hemispherical crowns

Official text — not yet verifiedGazette 1 Oct 2026 · printed p. 562

Not yet checked against the official Gazette; verify before relying on it.

Reproduced from the Gazette of India · verification status above

89. Hemispherical crowns.─ (1) The segments for hemispherical shell crown plates shall be pressed in one heat to correct curvature and shall be butt-welded together in accordance with Figures 12/3, 12/4, 12/5 or 12/6. The cylindrical portion of the crown shall be tangential to the hemispherical portion.

(2)Where hemispherical furnace crowns are pressed from one plate, they shall be pressed to form by machine in progressive stages without thinning and shall be annealed on completion.

Figures cited in this regulation (4, exact crops of the Gazette)

Gazette Fig. 12/3
Fig. 12/3(no caption printed with this figure)
View Gazette page 798 · figure catalogue
Reconstructed CAD: DXF · SVG · Preview (redrawn, checked against the print; technical review pending)
Gazette Fig. 12/4
Fig. 12/4(no caption printed with this figure)
View Gazette page 798 · figure catalogue
Reconstructed CAD: DXF · SVG · Preview (redrawn, checked against the print; technical review pending)
Gazette Fig. 12/5
Fig. 12/5(no caption printed with this figure)
View Gazette page 798 · figure catalogue
Reconstructed CAD: DXF · SVG · Preview (redrawn, checked against the print; technical review pending)
Gazette Fig. 12/6
Fig. 12/6(no caption printed with this figure)
View Gazette page 798 · figure catalogue
Auto-traced outline: SVG · DXF (not to scale, may copy print defects)
Independent explanation — not the law · draft · engineer review in progress

In short

Regulation 89 sets how hemispherical shell crowns and furnace crowns are formed.

Key points

  • (1) Segments of hemispherical shell crown plates are pressed in one heat to the correct curvature and butt-welded together as shown in Figures 12/3, 12/4, 12/5 or 12/6. The cylindrical part of the crown must be tangential to the hemispherical part.
  • (2) Hemispherical furnace crowns pressed from one plate are pressed by machine in progressive stages without thinning, and annealed on completion.

Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.

Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).

Orientation hints (unverified)

These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.

Historical 1950-edition reg.Heading as OCR'dHeading similaritySource image
595Hemispherical Furnacesof Vertical Boilers79%Chapter XII (DPIIT scan), image 14
IBR 1950 regulation 595 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 595 page for its amendments.

Reg. 593, Reg. 594, Reg. 595

Plain Furnaces of Vertical Boilers

The maximum working pressure of Plain Furnaces of Vertical boilers shall be the lesser of the two values obtained by Equations XII/25 and XII/26.

Where,

D = external diameter of the firebox in inches. Where the firebox is tapered the diameter taken shall be the mean of that at the top and at the bottom where it meets the substantial support from the flange or ring.

L is length of the firebox in inches between points of substantial support measured from the commencement of flange curvature or from the foundation connection, or from a row of screwed stays which comply with Regulations 550(b), 585(b), whichever is applicable.

In no case, however, shall the thickness be more than 7/8 inch. For fireboxes under 2 feet and 6 inches in diameter, the thickness shall be not less than 5/16 inch and for fireboxes 2 feet and 6 inches in diameter and over the thickness shall be not less than 3/8 inch.


Reg. 594

Corrugated Fireboxes of Vertical Boilers

For the semi-spirally corrugated fireboxes of ‘Sentinel’ standard motor wagon boilers the working pressure shall be determined by the following formula-

W.P. = C(t-1) Equation XII/29
D

W.P. is working pressure in pounds per square inch.
t is thickness of the firebox plate in thirty seconds of an inch.
D is mean of the external diameters of firebox measured over the plain part at each end at commencement of curvature of flange.
C = 390.

No corrugated furnace shall be less than 3/8 inch thick.
 

Reg. 595

Hemispherical Furnaces of Vertical Boilers

When furnaces are hemispherical in form and subject to pressure on the convex side and are without support from stays of any kind the maximum working pressure shall be found by the following formula:-

W.P. = 275(t-1) Equation XII/30
R

W.P. is working pressure in pounds per square inch.
t is thickness of the top plate in thirty seconds of an inch.
R is outer radius of curvature of the furnace in inches.
The thickness of these furnaces shall in no case exceed 7/8 inch

Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.

Instrument
Indian Boiler Regulations, 2026 (made by the Central Boilers Board under s.40 of the Boilers Act, 2025)
Notification
F.No. P-30014/3/2021-Boiler dated 7 Aug 2026
Published
Gazette of India, Extraordinary, Part III Sec. 4, No. 596, 1 Oct 2026 (CG-DL-E-06102026-276813)
In force
1 Oct 2026 (reg. 1(3): date of publication in the Official Gazette)
Printed Gazette page
562
PDF page index
562 · open official e-Gazette PDF
Extraction
pdftotext layout mode, sequential regulation detector · text hash 7d3a575094eaa1df
Verification
Official text — not yet verified
Amendments checked
None known after 1 Oct 2026 as of build date (not a guarantee). Amendment log
How to cite

Indian Boiler Regulations, 2026, reg. 89, Regulation 89, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.562. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).

The citation refers to the government publication. Cite the Gazette, not this website.

Help improve this page

Engineers like you keep IBRsource accurate. Every checked correction or tip helps the next reader.