Indian Boiler Regulations, 2026 · Chapter 3 · Construction and Workmanship
Regulation 131. Insufficient thickness of end plates
Not yet checked against the official Gazette; verify before relying on it.
131. Insufficient thickness of end plates.─ (1) In cases where the thickness of the end plate is insufficient for this purpose the mountings shall be joined to suitable steel seatings as provided in regulation 126.
(2)The following constructions as to stand pipes attached to shells and end plates shall be permissible:
(i)Where the internal diameter of the stand pipe does not exceed 25 mm, the standpipe may be screwed into the plate and fitted with a nut on the waterside.
(ii)Where the internal diameter of the standpipe exceeds 25 mm but does not exceed 51 mm, it may be screwed in and seal-welded.
(iii)Where the diameter of the standpipe exceeds 51 mm, it may be welded to the end plate.
(3)The foregoing provisions as to the stand pipe shall be regulated by the following conditions:
(i)When stand pipes are screwed, the screwing shall be of Standard Pipe Thread,
(ii)Where stand pipes, saddles or other forms of seatings are fabricated by fusion welding they shall be stress relieved by heat treatment before attachment to the boiler,
(iii)Where the bore of the stand pipe or seating and the hole in the plate do not exceed 127 mm plus twice the thickness of the plate, the seating may be welded to the plate without subsequent heat treatment of the weld so made. Where the hole in the plate exceeds 127 mm plus twice the thickness of the plate, the plate to which seating is attached shall be stress relieved by heat treatment.
In short
Where an end plate is too thin for direct attachment, mountings must be joined to steel seatings as in regulation 126. Regulation 131 also sets how stand pipes may be attached, by size.
Key points
- (2)(i) Internal diameter not exceeding 25 mm: screwed into the plate with a nut on the water side.
- (2)(ii) Over 25 mm up to 51 mm: screwed in and seal-welded.
- (2)(iii) Over 51 mm: may be welded to the end plate.
- (3)(i) Screwed stand pipes use Standard Pipe Thread.
- (3)(ii) Stand pipes, saddles or seatings fabricated by fusion welding must be stress relieved before attachment.
Watch out
- (3)(iii) If the bore and plate hole do not exceed 127 mm plus twice the plate thickness, the seating may be welded on without heat treating that weld. Above that, the plate must be stress relieved.
Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.
Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).
Orientation hints (unverified)
These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.
| Historical 1950-edition reg. | Heading as OCR'd | Heading similarity | Source image |
|---|---|---|---|
| 33 | Plates | 100% | Chapter II (DPIIT scan), image 3 |
| 403 | Thickness of Butt | 83% | Chapter X (DPIIT scan), image 1 |
| 113 | Flat End Plates | 80% | Chapter III (DPIIT scan), image 2 |
Amendment history of the candidate IBR 1950 regulations: Reg. 113 (1 amendment)
IBR 1950 regulation 33 as last published in the DPIIT web edition (archived 2022)
Unofficial archived copy, not verified; see the regulation 33 page for its amendments.
| Reg. 33 MATERIALS OF CONSTRUCTION COPPER PLATES, STAY AND RIVET BARS |
| (a) Process.- The copper shall be fire-refined or electrolytic and hot-rolled from suitable cakes. (b) Chemical Composition.- The chemical composition of the plates shall be as follows:-
(c) Freedom from defects.- The plates shall be clean, smooth and free from defects and shall have a workmanlike finish. They shall be thoroughly annealed. (d) Rolling Margin.- No plate shall be under the specified thickness at any part, not more than 5% over the calculated weight. The scrap margin, partly sheared and left attached, shall be not less than 3 inches at the ends and 1½ inches at each side. (e) Tensile Tests.- One tensile test shall be taken from each plate as rolled. The tensile breaking strength, from Standard Test Piece A, shall not be less than 14 tons per sq. inch with an elongation of not less than 35%. (f) Hot and Cold Bend tests.- One hot (temperature between 1200°F and 1400°F) and one cold bend test shall be taken from each plate as rolled. For either hot or cold bend tests, the test piece shall withstand being doubled over without fracture until the sides are touching and parallel. |
IBR 1950 regulation 403 as last published in the DPIIT web edition (archived 2022)
Unofficial archived copy, not verified; see the regulation 403 page for its amendments.
| Reg. 400, Reg. 401, Reg. 402, Reg. 403, Reg. 404 RIVETED STEEL BOILERS
Reg. 401 Working Pressure of Shells
Reg. 402
Reg. 404
|
IBR 1950 regulation 113 as last published in the DPIIT web edition (archived 2022)
Unofficial archived copy, not verified; see the regulation 113 page for its amendments.
| Reg. 113 END PLATES Flat End Plates
|
Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.


Indian Boiler Regulations, 2026, reg. 131, Regulation 131, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.581–582. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).
The citation refers to the government publication. Cite the Gazette, not this website.