Regulation 96. Furnaces of vertical boilers

Official text — not yet verifiedGazette 1 Oct 2026 · printed pp. 564–565

Not yet checked against the official Gazette; verify before relying on it.

Reproduced from the Gazette of India · verification status above

96. Furnaces of vertical boilers.─ (1) The furnaces of vertical boilers may be constructed in one or more lengthwise sections, each section being rolled from one plate to a full circle. In such cases, the component sections may be jointed circumferentially by electrically butt welding and shall be stress relieved in accordance with regulation 123.

(2)In the case of vertical boilers where tube plates form part of the firebox, the tube plate portion may be constructed in two vertical sections and the vertical seams when welded shall be stress relieved. The maximum permissible variation in diameter, at any cross-section shall not exceed 6 mm for fireboxes up to 900 mm in diameter, or 10 mm for fireboxes over 900 mm in diameter, or half the thickness of the plate whichever is greater.

(3)Circular furnaces shall preferably be tapered, a tapper of 38 mm in diameter per 300 mm of height being recommended. The minimum water space at the bottom between the furnaces and the shell shall not be less than 50 mm for boilers up to 760 mm in diameter and shall be not less than 63 mm for boilers over 760 mm diameter.

(4)The method of welding shall be in accordance with regulation 151. Flats formed in the firebox for the insertion of water tubes shall have ample radius at the junction of the flat and the curved surfaces and shall be free from sharp corners or tool marks. The plate shall not be unduly thinned.

(5)Ogee flanging where integral with the firebox or in a separate ring shall preferably be formed in one heat by suitable machinery and shall be allowed to cool gradually to avoid internal stresses. Rings of fire holes mouthpieces or foundation rings shall be made of mild steel. Z sections shall not be used for foundation rings.

(6)Furnaces of vertical type boilers may be attached to the shell at the fire hole by a circular ring of substantial section fusion welded to shell and firebox. The opening in the shell for fire hole shall be substantially compensated by a ring welded on the outside of the shell plate.

(7)At the fire hole the firebox plate and the shell plate may be flanged and fusion welded together.

Referenced provisions

Reg. 123 · Reg. 151

Independent explanation — not the law · draft · engineer review in progress

In short

Regulation 96 sets construction rules for the furnaces of vertical boilers: sections and welds, circularity, taper, water space and fire hole attachments.

Key points

  • (1) Furnaces may be in one or more lengthwise sections, each rolled from one plate. Sections may be joined circumferentially by electric butt welding and stress relieved under regulation 123.
  • (2) Where tube plates form part of the firebox, that portion may be in two vertical sections, with welded seams stress relieved. The diameter variation limit is 6 mm for fireboxes up to 900 mm diameter, 10 mm over 900 mm, or half the plate thickness, whichever is greater.
  • (3) Circular furnaces are preferably tapered, with 38 mm in diameter per 300 mm of height recommended. Minimum bottom water space between furnace and shell: 50 mm for boilers up to 760 mm diameter, 63 mm for larger boilers.
  • (4) Welding follows regulation 151. Flats for water tubes need ample radius, no sharp corners or tool marks, and no undue thinning.
  • (5) Ogee flanging is preferably formed in one heat and cooled gradually. Fire hole rings, mouthpieces and foundation rings are mild steel.
  • (6), (7) The furnace may be attached at the fire hole by a welded ring, with the shell opening compensated by an external ring. Alternatively, firebox and shell plates may be flanged and fusion welded together.

Watch out

  • Z sections must not be used for foundation rings.

Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.

Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).

Orientation hints (unverified)

These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.

Historical 1950-edition reg.Heading as OCR'dHeading similaritySource image
596Foundations of Vertical Boiler Furnaces84%Chapter XII (DPIIT scan), image 14
122Furnaces of Horizontal Boilers83%Chapter III (DPIIT scan), image 3
221Corrugated Furnaces of Horizontal Boilers81%Chapter IV (DPIIT scan), image 14
IBR 1950 regulation 596 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 596 page for its amendments.

Reg. 596, Reg. 597

Foundations of Vertical Boilers Furnaces

When circular furnaces of fireboxes of vertical boilers are not connected to the shell crown by uptake tube, smoke tubes or bolt stays and the whole load on the firebox vertically is borne by the bottom part of the firebox where it is connected to the shell the working pressure for the part, if firebox is joggled out to meet the shell or if any ogee ring is fitted, shall not exceed that found by the following formula:-

W.P. = C(t-1)² Equation XII/31
D(D-D1)

W.P. is working pressure in pounds per square inch.
t is thickness of the joggled firebox plate or ogee ring in thirty seconds of an inch.
D is inside diameter of the boiler shell in inches.
D1 is outside diameter of the joggled firebox at the commencement of curvature
Above joggled part or the outside diameter of the firebox where it joins the ogee ring.
C = 140 for Ogee rings (see Fig XII/26 and XII/27.
C = 100 where ‘U’ ring section is used (see Fig. XII/28)


Reg. 597

Foundations of Loco-type Boiler Fireboxes

Where the firebox roof in loco-type boilers is, not stayed direct to the external casing crown or to girders carried by the casing or if not connected to the casing by slings the working pressure for the parts, if plates are joggled out to meet the casing or if an ogee ring is fitted, shall not exceed that found by the following formula:-

W.P. = 70 (t-1) x (L+W)
Equation XII/32
L+W(W-W1)

WP is working pressure in pounds per square inch.
t  is thickness of the joggled firebox side plates or fire hole plate (whichever is less) or ogee ring in thirty seconds of an inch.
L  is length of firebox casing in inches measured between the water sides of front end plate and saddle plate at the foundation seam.
W  is width of firebox casing in inches measured between the water side of casing side plates at the foundation seam.
W1  is width of firebox in inches measured between the water sides of firebox side plates at the commencement of curvature above joggled part or where it joins the ogee ring.


Where only a comparatively narrow strip of the firebox roof is stayed directly to the casing crown the area so stayed shall be deducted from the area represented by LXW in the bottom line of the formula thus:

(L X W – A)(W-W1) and so used in Equation XII/32 in determining the working pressure for the parts, “A” being the area in square inches of the part of roof supported by the casing crown.
IBR 1950 regulation 122 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 122 page for its amendments.

Reg. 122
FURNACES
Furnaces of Horizontal boilers

a) The sections of the internal flues shall each be in one plate and shall be bent while cold to circular form and shall be welded longitudinally.
b) The maximum permissible variation in diameter at any cross section shall not exceed the thickness of the plate.
c) The weld shall be placed at the lower part of the flues, and shall break joint in successive sections by at least 12 inches.
d) Each flange for the circular seams shall be formed at one heat by suitable machinery.
e) The sections shall be allowed to cool gradually to avoid internal stresses.
f) The caulking edges of all flue flanges shall be machined or machine gas cut.
g The circular seams shall be arranged so that they do not fall in line with those of the adjacent flue or with the circumferential seams of the shell and are at least 6 inches apart.
h) When flues are flanged for attachment to both end plates the total length of each completed flue shall not exceed the length of the shell measured from the inner surface of the back end plate to the inner surface of the front end plate, both adjacent to the shell.
i) Where the flues are flanged for attachment to the end plates, the end sections shall be 1/16 inch thicker than the remaining sections, except in cases where the calculated thickness is over 13/16 inch, when the end section shall be 7/8 inch in thickness.
j) The flanged portion of furnace rings shall have radius of curvature of not less than 1 inch on water side.
k) Sections of corrugated flues may be fusion butt welded circumferentially and afterwards stress relieved by heat treatment.
l) As an alternative to Adamson flanges, furnaces which are partly fitted with corrugated sections shall be strengthened by means of suitable stiffening rings adequately welded to the furnaces. The moment of inertia of the stiffener shall be not less than that required by Regulation 592(b). In no case shall a flat stiffener be less than 63 mm. x 13 mm. (2½” x ½”).

IBR 1950 regulation 221 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 221 page for its amendments.

Reg. 220, Reg. 221, Reg. 222

FURNACES

Plain Furnaces of Horizontal Boilers

For plain furnaces or furnaces strengthened by Adamson or other joints or stiffeners of sufficient strength and for the semi-cylindrical tops of fire-boxes and bottom of combustion chambers where the sides are securely stayed, the working pressure shall not exceed the smaller of the values obtained from the following formulae :-
W. P. = C X (t - 1)2 Eqn.(57)
D ( L + 24 )

W. P. = C1 X {10 ( t - 1) - L ) Eqn.(58)
D

Where
d = the external diameter of the furnace or chamber top or bottom in inches

t = the thickness of the furnace plate in 32nds of an inch.

L = the length of the furnace or other part in inches measured between points of substantial support, i.e. centres of rows of rivets in end seams or commencement of curvature of flange, whichever is applicable.

C = 1450 where the longitudinal seams of steel furnaces are welded and 1300 where they are riveted,

C = 725 where the longitudinal seams of circular copper fireboxes or furnaces are fitted with double butt straps and 650 where they are lapped,

C1 = 50 where the longitudinal seams of steel furnaces are welded and 45 where they are riveted,

C1 = 25 where the longitudinal seams of circular copper fireboxes or furnaces are fitted with double butt straps and 22.5 where they are lapped.

Reg. 221

FURNACES

Corrugated Furnaces of Horizontal Boilers

The maximum working pressure to be allowed on corrugated furnaces shall be determined by the following formula -
W. P. = C ( t - 1 ) Eqn.(59)
D

where
D is the least external diameter in inches measured at the bottom of the corrugations on the water side.

t is the thickness of the furnace plate in 32nds of an inch measured at the bottom of the corrugation or chamber,

C = 480 for the Fox, Morrison, Deighton, Purves,, and other similar furnaces and 510 for the leeds Forge Bulb Suspension Furnace.

Reg. 222

FURNACES

Plain Furnaces of Vertical Boilers

The same formulae as for the plain furnaces of horizontal boilers shall be used, but where the furnaces are tapered the diameter to be taken for calculation purposes shall be the mean of that at the top and of that at the bottom where it meets the substantial support from flange or ring. The length for the same purpose shall be the distance from the centre of the row of rivets connecting the crown and the body of the furnace to the substantial support at the bottom of the furnace, or to a row of screwed stays connecting the furnace to the shell, provided that the pitch of stays at the furnace does not exceed 14 times the thickness of the furnace plate when the stays are riveted at their ends or 16 times when the stays are fitted with nuts. Such screwed stays shall be in diameter over the threads not less than twice the thickness of the furnace plate and in no case less than 3/4" diameter {See Reg.135 (d)}.

Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.

Instrument
Indian Boiler Regulations, 2026 (made by the Central Boilers Board under s.40 of the Boilers Act, 2025)
Notification
F.No. P-30014/3/2021-Boiler dated 7 Aug 2026
Published
Gazette of India, Extraordinary, Part III Sec. 4, No. 596, 1 Oct 2026 (CG-DL-E-06102026-276813)
In force
1 Oct 2026 (reg. 1(3): date of publication in the Official Gazette)
Printed Gazette page
564–565
PDF page index
564–565 · open official e-Gazette PDF
Extraction
pdftotext layout mode, sequential regulation detector · text hash 096a1852802b3081
Verification
Official text — not yet verified
Amendments checked
None known after 1 Oct 2026 as of build date (not a guarantee). Amendment log
How to cite

Indian Boiler Regulations, 2026, reg. 96, Regulation 96, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.564–565. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).

The citation refers to the government publication. Cite the Gazette, not this website.

Help improve this page

Engineers like you keep IBRsource accurate. Every checked correction or tip helps the next reader.