Indian Boiler Regulations, 2026 · Chapter 3 · Construction and Workmanship

Regulation 113. Breathing space

Official text — not yet verifiedGazette 1 Oct 2026 · printed pp. 569–570TableFigure referenced

Not yet checked against the official Gazette; verify before relying on it.

Reproduced from the Gazette of India · verification status above

113. Breathing space.─(1) Gusset stays shall be so arranged as to allow sufficient breathing space around furnace connections and the tube nests.

(2)For Lanchashire boilers, the proportions shown in the table below are recommended for portion of the end plates above the furnaces and flues.

Table 3/3

Sl.
No.
Thickness of End PlateL (Fig.3/8)L (Fig. 3/9)
(1)(2)(3)(4)
mmmmmm
113228254
214254254
316279309
417309330
519309330
621309330
7Above 21317343

Table structure read from the Gazette PDF, page 569. Verification status as for the text above.

Show original extracted text (diagnostic, not authoritative)
Sl.  Thickness of End Plate    L (Fig.3/8)          L (Fig. 3/9)

No.                                                      (4)
                                                        mm
(1)            (2)             (3)                      254
                                                        254
               mm              mm                       309
                                                        330
1              13              228                      330
                                                        330
2              14              254                      343

3              16              279

4              17              309

5              19              309

6              21              309

7    Above 21                  317

     Fig. 3/8                             Fig. 3/9

(3)Fig. 3/8 shows the breathing space recommended for the following conditions: Flat end, furnace or flues flanged for attachment to end plate, furnaces and flues formed with Adamson flanged seams.

(4)Fig. 3/9 shows similar conditions to Fig. 3/8 except that the end plate is flanged outwards for the furnace or flue ring connection, the breathing spaces allowed being 25 mm more than those for the same thickness of plate in Fig. 3/8

(5)Where a corrugated section not less than 1830 mm long is included in each internal flue or a Lancashire boiler, the dimensions given in the table above may be reduced by approximately 38 mm throughout.

(6)It is recommended that the breathing space below the furnaces and flues shall be approximately one half of the dimensions given in the table above. Whereas it is desired to use any other arrangement which gives a greater or less degree or flexibility, the amount of breathing space shall be specially considered and modified as the necessity of the case requires.

(7)For Gusset stays above tube nests, as fitted in waste heat boilers without internal furnaces, a breathing space of 203 mm from the center line of the top tubes of the center of the toe rivets of the gusset angles is recommended (see Fig. 3/9).

Parts of this extracted text look garbled; read the Gazette page before using any value.

Tables and formulae are shown in their extracted layout. Alignment, superscripts and subscripts may be lost. The Gazette page image is authoritative.

Figures cited in this regulation (2, exact crops of the Gazette)

Gazette Fig. 3/8
Fig. 3/8(no caption printed with this figure)
View Gazette page 569 · figure catalogue
Auto-traced outline: SVG · DXF (not to scale, may copy print defects)
Gazette Fig. 3/9
Fig. 3/9(no caption printed with this figure)
View Gazette page 569 · figure catalogue
Auto-traced outline: SVG · DXF (not to scale, may copy print defects)
Independent explanation — not the law · draft · engineer review in progress

In short

Regulation 113 requires gusset stays to leave enough breathing space (flexibility) around furnace connections and tube nests, and gives recommended dimensions for Lancashire boilers.

Key points

  • (1) Gusset stays must allow sufficient breathing space around furnace connections and tube nests.
  • (2) Table 3/3 gives recommended dimension L above the furnaces and flues for each end plate thickness, for the arrangements in Fig. 3/8 and Fig. 3/9.
  • (3) Fig. 3/8 covers flat ends with furnaces or flues flanged to the end plate and Adamson flanged seams.
  • (4) Fig. 3/9 is the same, except the end plate is flanged outwards for the furnace or flue ring. Breathing spaces are 25 mm more than in Fig. 3/8.
  • (5) Where each internal flue includes a corrugated section at least 1830 mm long, the tabulated dimensions may be reduced by about 38 mm.
  • (6) Below the furnaces and flues, about one half of the tabulated dimensions is recommended. Other arrangements need special consideration of the breathing space.
  • (7) For gusset stays above tube nests in waste heat boilers without internal furnaces, 203 mm is recommended from the centre line of the top tubes to the centre of the gusset angle toe rivets.

Watch out

  • These dimensions are stated as recommendations. The Table 3/3 columns are misaligned in the extracted text, so check the Gazette page for the values.

Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.

Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).

Orientation hints (unverified)

These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.

Historical 1950-edition reg.Heading as OCR'dHeading similaritySource image
141Breathing d furnace Conner a the table below are re75%Chapter III (DPIIT scan), image 7
IBR 1950 regulation 141 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 141 page for its amendments.

Reg. 141
GIRDER STAYS
Breathing Space

a) Gusset stays shall be so arranged as to allow sufficient breathing space around furnace connections and tube nests.
b) For Lancashire boilers the proportions shown in the table below are recommended for the portion of the end plates above the furnaces and flues.

Thickness of End Plates L-
(Fig.8)
L-
(Fig.9)
Inches Inches Inches
½ 9 10
9/16 10 10
5/8 11 12
11/16
¾
13/16
12 13
Above 13/16 12½ 13½
c) Fig. 8 shows the breathing space recommended for the following conditions: Flat end, furnace or flues flanged for attachment to end plate, furnaces and flues formed with Adamson flanged seams.
d) Fig. 9 shows similar conditions to Fig. 8 except that the end plate is flanged outwards for the furnace or flue ring connection, the breathing spaces allowed being 1 inch more than those for the same thickness of plate in Fig.8.
e) Where a corrugated section not less than 6 feet long is included in each internal flue of a Lancashire boiler, the dimensions given in the table above may be reduced by approximately 1½ inches throughout.
f) It is recommended that the breathing space below the furnaces and flues shall be approximately one half the dimensions given in the table above. Whereas it is desired to use any other arrangement which gives a greater or less degree of flexibility, the amount of breathing space shall be specially considered and modified as the necessity of the case requires.
g) For gusset stays above tube nests, as fitted in waste heat boilers without internal furnaces, a breathing space of 8 inches from the centre line of the top tubes to the centre of the toe rivets of the gusset angles is recommended (see Fig. 9).

Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.

Instrument
Indian Boiler Regulations, 2026 (made by the Central Boilers Board under s.40 of the Boilers Act, 2025)
Notification
F.No. P-30014/3/2021-Boiler dated 7 Aug 2026
Published
Gazette of India, Extraordinary, Part III Sec. 4, No. 596, 1 Oct 2026 (CG-DL-E-06102026-276813)
In force
1 Oct 2026 (reg. 1(3): date of publication in the Official Gazette)
Printed Gazette page
569–570
PDF page index
569–570 · open official e-Gazette PDF
Extraction
pdftotext layout mode, sequential regulation detector · text hash a3da3699461a6f1c
Verification
Official text — not yet verified
Amendments checked
None known after 1 Oct 2026 as of build date (not a guarantee). Amendment log
How to cite

Indian Boiler Regulations, 2026, reg. 113, Regulation 113, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.569–570. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).

The citation refers to the government publication. Cite the Gazette, not this website.

Help improve this page

Engineers like you keep IBRsource accurate. Every checked correction or tip helps the next reader.