Indian Boiler Regulations, 2026 · Chapter 3 · Construction and Workmanship
Regulation 104. Nuts and Washers for Stays
Not yet checked against the official Gazette; verify before relying on it.
104. Nuts and Washers for Stays.─ (1) The washers shall be at least 2½ times the diameter of the threaded portion of the stay and not less than 6 mm in thickness.
(2)The thickness of the external nuts shall be at least equal to the diameter of the threaded portion of the stay. Where bar stays pass through clearing holes in end plates, internal nuts of a thickness not less than two-thirds of the diameter of the threaded portion of the stay shall be fitted.
In short
Regulation 104 sets the minimum size of washers and nuts for stays, related to the diameter of the stay's threaded portion.
Key points
- (1) Washers are at least 2½ times the threaded diameter, and at least 6 mm thick.
- (2) External nuts are at least as thick as the threaded diameter.
- (2) Where bar stays pass through clearing holes in end plates, internal nuts at least two-thirds of the threaded diameter thick must be fitted.
Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.
Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).
Orientation hints (unverified)
These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.
| Historical 1950-edition reg. | Heading as OCR'd | Heading similarity | Source image |
|---|---|---|---|
| 132 | Nuts and Washers for Stays | 100% | Chapter III (DPIIT scan), image 6 |
IBR 1950 regulation 132 as last published in the DPIIT web edition (archived 2022)
Unofficial archived copy, not verified; see the regulation 132 page for its amendments.
| Reg. 130, Reg. 131, Reg. 132 STAYS Bar Stays Bar stays shall not be welded at any part. They shall preferably have plus threads, the ends of the stays being upset or the middle portion being reduced for this purpose. Stay bars which have been worked in the fire shall be subsequently annealed. Reg. 131 STAYS Longitudinal Stays
Reg. 132 STAYS Nuts and Washers for Stays
|
Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.

Indian Boiler Regulations, 2026, reg. 104, Regulation 104, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.567. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).
The citation refers to the government publication. Cite the Gazette, not this website.