Regulation 109. Stay nuts

Official text — not yet verifiedGazette 1 Oct 2026 · printed p. 568

Not yet checked against the official Gazette; verify before relying on it.

Reproduced from the Gazette of India · verification status above

109. Stay nuts.─ (1) Nuts of screw stays in combustion chambers and firebox shall not be less than 19 mm thick for stays up to 38 mm diameter over threads, 22 mm thick for 41 mm and 44 mm stays, 25 mm thick for 47 mm and 51 mm stays, and 28 mm thick for stays over 51 mm in diameter.

(2)The nuts shall be made of solid mild steel or of iron which shall be without weld, if exposed to flame.

Independent explanation — not the law · draft · engineer review in progress

In short

Regulation 109 sets the minimum thickness and material of nuts on screw stays in combustion chambers and fireboxes.

Key points

  • (1) Minimum nut thickness by stay diameter over threads: 19 mm for stays up to 38 mm; 22 mm for 41 mm and 44 mm stays; 25 mm for 47 mm and 51 mm stays; 28 mm for stays over 51 mm.
  • (2) Nuts are solid mild steel, or iron without weld, if exposed to flame.

Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.

Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).

Orientation hints (unverified)

These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.

Historical 1950-edition reg.Heading as OCR'dHeading similaritySource image
581Stay tubes74%Chapter XII (DPIIT scan), image 9

Amendment history of the candidate IBR 1950 regulation: Reg. 581 (3 amendments)

IBR 1950 regulation 581 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 581 page for its amendments.

Reg. 580, Reg. 581

Pitch of tubes

The spacing of tube holes shall be such that the minimum width in inches of any ligament between the tube holes shall be not less than:-

D + ½
8

alternatively,

the thickness and cross-section of the plate between the tube holes shall be not less than

0.125D+0.2=minimum thickness in inches.
0.17D+0.025=minimum cross-section in square inches where D is diameter of the tube holes in inches.

In no case shall the minimum thickness of any tube plate in the tube area be less than the following limits:-

T=1/2 inch, Where the diameter of the tube holes does not exceed 2 inches.
T=9/16 inch, Where the diameter of the tube hole is greater than 2 inches.



Reg. 581

Stay tubes

Stay tubes shall be of steel seamless or electrically resistance welded.
a) Minimum thickness of stay tubes – The minimum thickness of stay tubes shall be as per regulation 148.
b) The maximum working pressure for screwed in stay tube shall be calculated by the following formula:

WP = 5900         1.28
[(D---------------/N )² - D1²]
Equation XII/16
A

D is diameter of the stay tube over threads in inches.
D1 is internal diameter of the tubes under the threads in inches.
N is number of threads per inch.

A is the area in square inches supported by one Stay tube, measured from centre to centre of stay tubes. When the area contains tubes or parts of tubes their aggregate area, calculated from their smallest external diameter of body when in tension and smallest internal diameter when in compression, shall be deducted from the area of the containing figure and the remainder used as A in the formula.

Where stay tubes have their thickness increased at the screwed, ends to provide for plus threads the increased thickness shall be obtained by up-setting and not by welding, and the tubes shall be subsequently annealed.

Stay tubes may be attached to the tube plates either by screwing or by metal arc welding.

Where stay tubes are screwed into the tube plates they shall be screwed with a continuous thread not finer than 11 threads per inch at both ends and shall be expanded into the tube plates, by roller expander and, if desired, may be seal welded.

Welded attachment of stay tubes be as shown in Figure XII/67,XII/67A,XII/68, ,XII/68A and XII/69.

Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.

Instrument
Indian Boiler Regulations, 2026 (made by the Central Boilers Board under s.40 of the Boilers Act, 2025)
Notification
F.No. P-30014/3/2021-Boiler dated 7 Aug 2026
Published
Gazette of India, Extraordinary, Part III Sec. 4, No. 596, 1 Oct 2026 (CG-DL-E-06102026-276813)
In force
1 Oct 2026 (reg. 1(3): date of publication in the Official Gazette)
Printed Gazette page
568
PDF page index
568 · open official e-Gazette PDF
Extraction
pdftotext layout mode, sequential regulation detector · text hash b55ca718a09465cd
Verification
Official text — not yet verified
Amendments checked
None known after 1 Oct 2026 as of build date (not a guarantee). Amendment log