312. Calculation of wasted shell.─(1)When any part is wasted and the Competent Person is doubtful of its fitness for the pressure, he shall cause one or more small holes to be bored and from them ascertain the average thickness of the parts from which he can satisfy himself by calculation, in accordance with the formula applicable to the part. He shall enter such gauging and calculations in the Memorandum of Inspection Book.
(2)In making calculations for a wasted part of a boiler shell, e.g., along the line of seating blocks of a Lancashire boiler, the Competent Person shall use the following formula:
2t x S Equation (8/1)
P = --------
D x F
Where, t = thickness of wasted plate, where thinnest in mm,
S = minimum tensile strength of material of shell in Kg/mm2,
D = internal diameter of shell in mm,
F = factor of safety, which shall not be less than 4.
P = maximum allowable working pressure in Kg/mm2
Tables and formulae are shown in their extracted layout. Alignment, superscripts and subscripts may be lost. The Gazette page image is authoritative.
In short
Regulation 312 tells the Competent Person how to check a wasted part of a boiler. If he doubts its fitness for the pressure, he has one or more small holes bored, finds the average thickness, and checks it by calculation with the formula for that part. The gauging and calculations go in the Memorandum of Inspection Book.
Key points
- (1) Thickness is found by boring small holes and averaging; but for a wasted shell, equation (8/1) in (2) uses the thickness of the wasted plate where thinnest.
- (2) For a wasted shell (for example along the seating blocks of a Lancashire boiler), Equation (8/1) gives the maximum allowable working pressure P from the thinnest wasted thickness t, minimum tensile strength S, internal diameter D and factor of safety F.
Watch out
- The factor of safety F must not be less than 4.
Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.
Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).
Orientation hints (unverified)
These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.
No candidate heading found in the historical print edition.
Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.


Indian Boiler Regulations, 2026, reg. 312, Regulation 312, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.711–712. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).
The citation refers to the government publication. Cite the Gazette, not this website.