Indian Boiler Regulations, 2026 · Chapter 2 · Materials of Construction
Regulation 67. Transverse test
Not yet checked against the official Gazette; verify before relying on it.
67. Transverse test.─(1)A transverse test bar cast in accordance with sub-regulation (1) of regulation 65 when placed on supports set at the distance shown in column 2 of Table 2/40 must sustain a load applied at the centre of not less than that shown in column 3 and must show before rupture a deflection not less than that shown in column 4.
(2)The supports and the point of application of the load shall be rounded to a radius of not less than 3 mm.
| Serial No. | Diameter of test bar | Distance between support | Minimum breaking load Grade A | Minimum deflection Grade A |
|---|---|---|---|---|
| (1) | (2) | (3) | (4) | (5) |
| 1. | mm. | mm. | kg | mm. |
| 2. | 15 | 228 | 240 | 1.8 |
| 3. | 22 | 305 | 538 | 2.5 |
| 4. | 30 | 457 | 885 | 3.8 |
| 5. | 40 | 457 | 1941 | 3 |
| 6. | 53 | 610 | 3020 | 3.8 |
Table structure read from the Gazette PDF, page 551. Verification status as for the text above.
Show original extracted text (diagnostic, not authoritative)
Serial No. Diameter of test bar Table 2/40 Minimum breaking Minimum deflection
load Grade A Grade A
(1) (2) Distance between (4) (5)
1. mm. support kg mm.
2. 15 (3) 240 1.8
3. 22 mm. 538 2.5
4. 30 228 885 3.8
5. 40 305 1941 3
6. 53 457 3020 3.8
457
610(3)If the diameter of a transverse test bar as cast varies within the limits specified in sub-regulation (1) of regulation 65,the equivalent breaking load for the test bar of standard diameter shall be calculated in accordance with the factors given in Appendix-B .
Parts of this extracted text look garbled; read the Gazette page before using any value.
Tables and formulae are shown in their extracted layout. Alignment, superscripts and subscripts may be lost. The Gazette page image is authoritative.
In short
Regulation 67 sets the transverse (bending) test for grey iron Grade A test bars: the support span, the minimum breaking load at the centre and the minimum deflection before rupture.
Key points
- (1) A bar cast to sub-regulation (1) of regulation 65 is placed on supports at the distance given in Table 2/40. It must carry at least the tabulated central load and show at least the tabulated deflection before it breaks.
- (2) The supports and the loading point are rounded to a radius of not less than 3 mm.
- (3) If the as-cast diameter varies within the permitted limits, the equivalent breaking load for the standard diameter is calculated with the factors in Appendix-B.
Watch out
- The columns of Table 2/40 are misaligned in the extracted text. Check the Gazette page for the exact span, load and deflection for each diameter.
Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.
Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).
Orientation hints (unverified)
These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.
| Historical 1950-edition reg. | Heading as OCR'd | Heading similarity | Source image |
|---|---|---|---|
| 90 | Transverse test | 100% | Chapter II (DPIIT scan), image 18 |
IBR 1950 regulation 90 as last published in the DPIIT web edition (archived 2022)
Unofficial archived copy, not verified; see the regulation 90 page for its amendments.
| Reg. 90 MATERIALS OF CONSTRUCTION GENERAL GREY IRON CASTINGS (GRADE A) Transverse test |
| A transverse test bar cast in accordance with Regulation 88(a)must when placed on supports set at the distance shown in column 2 of the following table sustain a load applied at the centre of not less than that shown in column 3 and must show before rupture a deflection not less than that shown in column 4. The supports and the point of application of the load shall be rounded to a radius of not less than 1/8 inch.
If the diameter of a transverse test bar as cast varies within the limits specified in Regulation 88(a) the equivalent breaking load for the test bar of standard diameter shall be calculated in accordance with the given factors in Appendix F. |
Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.

Indian Boiler Regulations, 2026, reg. 67, Regulation 67, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.551. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).
The citation refers to the government publication. Cite the Gazette, not this website.