Regulation 176. Dished end with opening

Official text — not yet verifiedGazette 1 Oct 2026 · printed pp. 612–614Figure referencedFormula / symbols

Not yet checked against the official Gazette; verify before relying on it.

Reproduced from the Gazette of India · verification status above

176. Dished end with opening.─ (1) (a) Holes cut in the heads (manholes or tube holes) shall be round or elliptical.

(b)Small size openings complying with conditions of sub-regulation (3) do not require any additional thickness of head or reinforcement of opening.

(c)Large size openings require an increase in thickness of the head, according to sub-regulation (2) or a reinforcement of the opening according to sub-regulation (4) .

(2)(a)The shape factor ‘K’ to be used in calculating the thickness of heads varies depending on the height of the head ‘H’ and on the dimension of the largest opening. The value of K is indicated in Fig. 4/21, by means of curves, each of which corresponds to a value of the ratio--

Where,                                            d
          d =                                 -------

                                            √ DT

diameter or the largest opening in the head (in the case of an elliptical opening, the larger diameter of the ellipse);

D = outside diameter of the head; and

T= minimum thickness after dishing.

(b)In addition, the following conditions shall be satisfied;

T
< 0.1 and

D d
< 0.5

D

(c)The same condition and the same curves apply for openings simply cut in the plate of the head as well as to those which are flanged inwards. In the latter case, the radius ‘r’ of the flanging (see Fig. 4/18) should not be smaller than 25 mm. The thickness of the flanged portion may be smaller than the calculated thickness ‘T’.

(d)Unreinforced openings and flanged-in openings in dished heads shall be arranged so that the distance from the edge of the head is not less than as shown in Fig. 4/19.

(e)In all case the width of the band separating two adjacent openings should, in projection, be at least equal to the diameter of the smallest opening as shown in Fig. 4/19.

(3)(a)Small openings which do not require any reinforcement; Fig. 4/21 indicates that, for a given ratio of H/D, the shape factor K of a plain head corresponds to a certain value of the ratio,

       d
    -------

√ DT

(b)Piercing of holes with a diameter smaller than or equal to that which corresponds to this value can thus be made without any reinforcement in a head, the thickness of which is equal to the minimum required for a plain head.

(c)The position of those openings shall however comply with the conditions stated in sub-regulation (2).

(4)(a)Reinforcement of large openings; large holes may be cut without increasing the thickness of the head provided they are sufficiently reinforced.

(b)The reinforcement may consist either of a welded nozzle or one or two reinforcing welded plates, or of a combination of these two procedures.

(c)To determine the strength of the construction, one shall proceed as follows (see Fig. 4/20) Let the imaginary diameter d’ of the opening be given by the formula.

A
d’ = d - ----

T

Where, d = actual diameter of the opening in the head (outside diameter of the nozzle);

T = minimum thickness of the head; and

A = effective cross-section of reinforcement.

(d)This effective area ‘A’ corresponds, within the Limits given below, with the actual cross-section of the reinforcing plates and with the cross-section of the nozzle decreased by the cross-section necessary to support the pressure, for those parts of the nozzle situated outside the internal surface of the head.

(e)The shape factor K can then be read from Fig. 4/21, corresponding to the ratio d’ / √DT

(f)The maximum limits for the area of reinforcement that shall be taken into account are

(a)L1 = √ 2RT for the width of a reinforcing plate;

(b)L2 = √ dTt for the length of a nozzle

Where,

R= internal radius of the spherical part of the head (or for elliptical heads the internal radius of curvature of the meridian at the centre of the opening).

Tt = actual thickness of the nozzle,

L1 and L2 = dimensions given in Fig. 4/20.

(g)The position of the outer edges of the reinforcement shall comply with the provisions of sub-regulation (2) and Fig. 4/19.

(h)In cases where the allowable stress of a part of the reinforcement is lower than that of the head, the corresponding area A should be multiplied by the ratio:

allowable stress of the reinforcement material
-------------------------------------------------------------

    allowable stress of the head material

Tables and formulae are shown in their extracted layout. Alignment, superscripts and subscripts may be lost. The Gazette page image is authoritative.

Figures cited in this regulation (4, exact crops of the Gazette)

Gazette Fig. 4/18: Head with Manhole (Elliptical or Torispherical)
Fig. 4/18Head with Manhole (Elliptical or Torispherical)
View Gazette page 609 · figure catalogue
Auto-traced outline: SVG · DXF (not to scale, may copy print defects)
Gazette Fig. 4/19: Opening in Heads
Fig. 4/19Opening in Heads
View Gazette page 610 · figure catalogue
Auto-traced outline: SVG · DXF (not to scale, may copy print defects)
Gazette Fig. 4/20: Reinforced opening
Fig. 4/20Reinforced opening
View Gazette page 610 · figure catalogue
Auto-traced outline: SVG · DXF (not to scale, may copy print defects)
See Gazette page
Fig. 4/21Graph of Shape Factor K for Dished Heads
Gazette p.611
Independent explanation — not the law · draft · engineer review in progress

In short

Regulation 176 sets the rules for openings in dished ends: shape, the shape factor K, when no reinforcement is needed, and how to reinforce large openings.

Key points

  • (1) Holes in heads must be round or elliptical. Small openings meeting (3) need no extra thickness or reinforcement; large ones need a thicker head (2) or reinforcement (4).
  • (2)(a) Shape factor K is read from Fig. 4/21, depending on head height H and the ratio of the largest opening d to √(DT), with D the outside diameter and T the minimum thickness after dishing.
  • (2)(b) T/D must be < 0.1 and d/D < 0.5.
  • (2)(c) The same applies to inward-flanged openings, with flange radius r not smaller than 25 mm.
  • (2)(d)–(e) Distance from the head edge and band width between openings must follow Fig. 4/19; the band must be at least the diameter of the smaller opening.
  • (3) A hole no larger than the value matching the plain-head K can be cut without reinforcement in a head of minimum plain-head thickness, if positioned as in (2).
  • (4) Large holes may be reinforced by a welded nozzle, reinforcing plates, or both. An imaginary diameter d' = d − A/T is used to read K, where A is the effective reinforcement area, limited to widths L1 = √(2RT) for plates and L2 = √(dTt) for nozzles.

Watch out

  • If reinforcement material has a lower allowable stress than the head, area A must be reduced by the ratio of the two allowable stresses.

Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.

Original drawings for this regulation

Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).

Orientation hints (unverified)

These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.

Historical 1950-edition reg.Heading as OCR'dHeading similaritySource image
408Dished End Plates with pressure on concave side79%Chapter X (DPIIT scan), image 2
428Dished End Plates with pressure on Concave Side79%Chapter X (DPIIT scan), image 8
632Dished end plates74%Chapter XV (DPIIT scan), image 3
IBR 1950 regulation 408 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 408 page for its amendments.

Reg. 408

Dished End Plates with pressure on concave side

Where an end plate is dished to semi-ellipsoidal or partially spherical form, the inside radius of dishing shall be not greater than the outside diameter of the flange(see Fig 23).

Wherever practicable, the inside corner radius shall be 12.5 per cent, of the inside diameter and in no case shall be less than 6 per cent. of the inside diameter.

For ends of semi-ellipsoidal from the ration of the major axis to the minor axis shall be not greater than 2.

Where an end plate is dished to semi-ellipsoidal or partially spherical form and has a flanged-in-manhole or access opening, the thickness shall be increased by not less than 15 per cent. of the thickness computed by the formula for an end plate without an opening, but in no case shall this increase be less than 1/8 inch.

The depth in inches of the flange G (see Fig 23) forming the access opening measured from the outer surface of the place at the minor axis of the opening shall be not less than:

Where
         ________
G=ÖT x W
T=thickness of the end plate in inches
W=length of minor axis in inches.

The corner radius of the manhole flange vm (see Fig. 23) shall be not less than 1 inch.

In case where full compensation is provided for an un-flanged opening cut in a dished end plate, no additional thickness is necessary.

Where it is not practicable to make a dished end plate in one piece, fusion welded seams welded from each side of the plate may be employed provided the appropriate constraints as given below are introduced into the formula for obtaining the thickness. The limits of pressure and diameter specified in Regulation 416 shall, however, apply.

The maximum working pressure shall be determined by the following formula but in no case shall the thickness at the edge of the flange for connecting to the shell be less than the thickness of the unpierced seamless shell as determined by Equation (1).

W.P.= (t-2) x C x S Equation (97)
D x K
Where,

t = thickness of plate in thirty-seconds of an inch.
WP = working pressure in pounds per square inch.
D = outside diameter of the flange in inches.
K = a factor dependent upon the ration h / D
Generally obtained from the curve shown in Figure 22 or by Equation 75 In no case shall K be taken as less than:

1.15 R or 0.12 D
D R
S = minimum ultimate stress of plate in tons per square inch.
C = constant as follows:
       a. Where the end plate is in one piece.
C = 35
       b. where the end plate is not one piece.
C = 32 where Class I requirements are complied with.
    = 27 where Class II requirements are complied with.

The thickness to be used in the formulae is the thickness of the end after manufacture and is applicable over the whole area of the end up to the point where for ends of partially spherical shape, the dishing radius joins the corner radius; from this point a gradual thinning is permissible up to a maximum of 10 per cent. of the thickness ‘t’ at the point where the corner radius joints the straight portion of the flanged end. A similar gradual thinning is permissible for ends of semi-ellipsoidal shape. This permissible reduction in thickness also applies to the flange for the manhole opening.

Where a dished end plate is pierced with more than one opening for electrodes or other fittings, the openings shall be so arranged as to provide an unpierced annulus not less than 2 in. wide measured from the center of the corner radius.

Where the diameter of such opening is not greater than 1-1/2 inches and the value of t

the ligament p-d is not less than I compensation is not required
P K

Where d is greater than 2-1/2 inches or p-d is less than I full compensation shall be
P K


provided where-

p = pitch of opening in inches.
d = diameter of openings in inches.
K = factor (see Equation above).
IBR 1950 regulation 428 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 428 page for its amendments.

Reg. 427, Reg. 428, Reg. 429, Reg. 430
TESTS FOR CLASS II FUSION WELDED SEAMS

Manholes and other openings in Shells

Manholes and other openings in boiler shells shall be placed away from any welded seam. Oval openings shall be arranged with their minor axis parallel to the longitudinal centre line of the boiler.

(a) Un-compensated openings shall comply with Regulation 187.
(b) Compensated openings shall comply with Regulations 170, 171, 186 and 279.


Reg. 428
TESTS FOR CLASS II FUSION WELDED SEAMS

Dished End Plates with pressure on Concave side

This shall comply with Regulation 408.



Reg. 429
TESTS FOR CLASS II FUSION WELDED SEAMS

Unstayed Flat End Plates

The working pressure of unstayed flat end plates shall comply with Regulation 412.

Where the diameter of the openings in an unstayed flat end plate is greater than 2½ inches or the pitch in inches is less than four times the diameter of the holes full compensation shall be provided as in Regulation 279.



Reg. 430
TESTS FOR CLASS II FUSION WELDED SEAMS

Thickness of Angle Rings

Thickness of angle rings shall comply with Regulation 379(a).

Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.

Instrument
Indian Boiler Regulations, 2026 (made by the Central Boilers Board under s.40 of the Boilers Act, 2025)
Notification
F.No. P-30014/3/2021-Boiler dated 7 Aug 2026
Published
Gazette of India, Extraordinary, Part III Sec. 4, No. 596, 1 Oct 2026 (CG-DL-E-06102026-276813)
In force
1 Oct 2026 (reg. 1(3): date of publication in the Official Gazette)
Printed Gazette page
612–614
PDF page index
612–614 · open official e-Gazette PDF
Extraction
pdftotext layout mode, sequential regulation detector · text hash 456d445aaad8a107
Verification
Official text — not yet verified
Amendments checked
None known after 1 Oct 2026 as of build date (not a guarantee). Amendment log
How to cite

Indian Boiler Regulations, 2026, reg. 176, Regulation 176, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.612–614. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).

The citation refers to the government publication. Cite the Gazette, not this website.

Help improve this page

Engineers like you keep IBRsource accurate. Every checked correction or tip helps the next reader.