Regulation 158. Tensile test pieces

Official text — not yet verifiedGazette 1 Oct 2026 · printed pp. 591–592Figure referenced

Not yet checked against the official Gazette; verify before relying on it.

Reproduced from the Gazette of India · verification status above

158. Tensile test pieces.─(1) (a)The dimension of the reduced tensile section shall be as shown in Fig.4/3 and the width of the reduced section shall be at least 25 mm.

(b)If the thickness of the plate does not exceed 30 mm, the thickness of the specimen shall be equal to the plate thickness and the plate surface of the specimen which shall be machined to take away the surface irregularities of the plate and the weld.

All dimensions are in mm.

Fig. 4/3: Reduced Section Tensile Specimen

(c)If the plate thickness exceeds 30 mm, the tensile test shall be carried out on several reduced section specimens, each having a thickness of at least 30 mm and a width at the effective cross-section of at least 25 mm. These Specimens shall be taken out of the test piece in such a way that the tensile test covers the whole thickness of the weld joints as shown in Fig. 4/4. In this case the result of the test of every test specimen concerned shall meet the requirements specified in sub-regulation (1) of regulation 159.

All dimensions are in mm.

Fig. 4/4: Reduced Section Tensile Specimen in Thick Plate

All dimensions are in mm.

Fig. 4/5: All-Weld Metal Test Specimen

(2)The dimensions of the all weld metal tensile test specimens shall be those given in Fig. 4/5. The diameter shall be the maximum possible, consistent with the cross-section of the weld but in no case more than 20 mm. The gauge length shall be equal to five times the diameter.

Referenced provisions

Reg. 159

Figures cited in this regulation (3, exact crops of the Gazette)

Gazette Fig. 4/3: Reduced Section Tensile Specimen
Fig. 4/3Reduced Section Tensile Specimen
View Gazette page 591 · figure catalogue
Reconstructed CAD: DXF · SVG · Preview (redrawn, checked against the print; technical review pending)
Gazette Fig. 4/4: Reduced Section Tensile Specimen in Thick Plate
Fig. 4/4Reduced Section Tensile Specimen in Thick Plate
View Gazette page 591 · figure catalogue
Reconstructed CAD: DXF · SVG · Preview (redrawn, checked against the print; technical review pending)
Gazette Fig. 4/5: All-Weld Metal Test Specimen
Fig. 4/5All-Weld Metal Test Specimen
View Gazette page 592 · figure catalogue
Reconstructed CAD: DXF · SVG · Preview (redrawn, checked against the print; technical review pending)
Independent explanation — not the law · draft · engineer review in progress

In short

Regulation 158 sets the dimensions of reduced-section and all-weld metal tensile test specimens.

Key points

  • (1)(a) The reduced section follows Fig. 4/3 and is at least 25 mm wide.
  • (1)(b) For plate up to 30 mm, specimen thickness equals plate thickness, machined only to remove surface irregularities of plate and weld.
  • (1)(c) For plate over 30 mm, several specimens are used, each at least 30 mm thick and 25 mm wide, together covering the whole joint thickness (Fig. 4/4). Every specimen must meet regulation 159(1).
  • (2) All-weld metal specimens follow Fig. 4/5. Diameter is the maximum the weld allows, but not more than 20 mm, with a gauge length of five times the diameter.

Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.

Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).

Orientation hints (unverified)

These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.

Historical 1950-edition reg.Heading as OCR'dHeading similaritySource image
91Tensile test100%Chapter II (DPIIT scan), image 18
259Tensile Test Pieces100%Chapter V (DPIIT scan), image 6
1Tensile test for joint77%Chapter V (DPIIT scan), image 5

Amendment history of the candidate IBR 1950 regulations: Reg. 259 (1 amendment) · Reg. 1 (1 amendment)

IBR 1950 regulation 91 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 91 page for its amendments.

Reg. 91
MATERIALS OF CONSTRUCTION

GENERAL GREY IRON CASTINGS (GRADE A)

Tensile test

A tensile test bar machined to the dimensions shown in Regulation 88(b) and tested with either plain or screwed ends must show a breaking strength of not less than that shown in the following table:-

Diameter of test bar
Minimum ultimate tensile stress – Grade A

Inches

Tons per sq. inch
0.6 12.5
0.875 12
1.2 11
1.6 10.5
2.1 10


Note – Self-aligning grips to ensure axial loading are recommended.

IBR 1950 regulation 259 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 259 page for its amendments.


Reg. 259
, Reg. 260 A, Reg. 260 B

Tensile Test Pieces

a)

Welded Joint:-

The dimensions of the reduced tensile section shall be those shown in figure. 18A. The width of the reduced section shall be at least 25 mm.

If the thickness of the plate does not exceed 30mm, the thickness of the specimen shall be equal to the plate thickness and the plate surface of the specimen shall be machined to take away the surface irregularities of the plate and the weld.

If the plate thickness exceeds 30 mm, the tensile test shall be carried out on several reduced section specimens, each having a thickness of at least 30 mm and a width at the effective cross-section of at least 25 mm. These specimens shall be taken out of the test piece in such a way that the tensile test covers the whole thickness of the weld joints as shown in figure 18B. In this case the result of the test of every test specimen concerned shall meet the requirements specified in regulation 260(a).
b) All weld metal: The dimensions of the all weld metal tensile test specimens shall be those given in figure 19.

The diameter shall be the maximum possible consistent with the cross-section of the weld but in no case more than 20mm. The gauge length shall be five times the diameter.



Reg. 260 

Tensile Tests

(a) Welded joint

The ultimate tensile stress shall be not less than the lower limit specified for the plate (see table under Reg. 234).


(b) All-weld Metal

The ultimate tensile stress shall be not less than the lower limit specified for the plate (see table under Regulation 234).

The elongation shall be not less than 20 per cent on a gauge length of four times the square root of the cross sectional area of the specimen, and the reduction in area not less than 35 per cent.

IBR 1950 regulation 1 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 1 page for its amendments.

Reg. 1
Short Title, Extent, Application and Commencement:

1) These Regulations may be called the Indian Boiler Regulations, 1950.
2) They extend to the whole of India, except the State of Jammu and Kashmir.
2a)

These Regulations generally apply to:-

(i) all boilers, including those working on the principles of natural circulation, forced circulation and forced flow with no fixed steam water line, and
(ii) to steam pipes.
3) They shall come into force at once

Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.

Instrument
Indian Boiler Regulations, 2026 (made by the Central Boilers Board under s.40 of the Boilers Act, 2025)
Notification
F.No. P-30014/3/2021-Boiler dated 7 Aug 2026
Published
Gazette of India, Extraordinary, Part III Sec. 4, No. 596, 1 Oct 2026 (CG-DL-E-06102026-276813)
In force
1 Oct 2026 (reg. 1(3): date of publication in the Official Gazette)
Printed Gazette page
591–592
PDF page index
591–592 · open official e-Gazette PDF
Extraction
pdftotext layout mode, sequential regulation detector · text hash d699d72c44cae0ea
Verification
Official text — not yet verified
Amendments checked
None known after 1 Oct 2026 as of build date (not a guarantee). Amendment log
How to cite

Indian Boiler Regulations, 2026, reg. 158, Regulation 158, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.591–592. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).

The citation refers to the government publication. Cite the Gazette, not this website.

Help improve this page

Engineers like you keep IBRsource accurate. Every checked correction or tip helps the next reader.