BETAIndependent engineering reference. Source-text verification is ongoing.Verification ongoing.Verification status →
IBRsourceIndian Boiler Regulations, made clear

Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)

Regulation 351 — Cast Steel Pipes

Unofficial DPIIT web edition · not verified1 amendment found

Text in the DPIIT web edition

Archived copy captured 03 Aug 2022 (Wayback Machine). The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.

Unofficial DPIIT web edition · archived 2022 · not checked against the Gazette
Reg. 351

Cast Steel Pipes

(a) The material shall comply with regulations 73 to 80.
b)

The maximum working pressure allowed on cast steel pipes shall be determined by the following formula:-

W. P. = 2 S ( t - .015D - C ) Eqn.(92)
D

where,

t = minimum thickness
W. P = Working Pressure
D = External diameter of pipe
S = Allowable working stress as specified in regulation 343.
C = 0.64 cm(0.25 in).


Maximum Permissible Working Stress for Carbon and Alloy Cast Steel Pipes
(See Regulation 351)

Lower value obtained in each case at the specified temperature calculated on the following basis:-

For service temperature at or
below 454°C (850°F)
T.S. or Et
2.7 1.5


For service temperature
above 454°C (850°F)
Et or Sr or Sc
1.5 1.5
Earlier text: the 2008 DIPP web edition

Cast Steel Pipes

(a)The material shall comply with regulations 73 to 80.

b)The maximum working pressure allowed on cast steel pipes shall be determined by the following formula:-

         2 S ( t - .015D - C )
W. P. =                    Eqn.(92)
                D

where,

t = minimum thickness

W. P = Working Pressure

D = External diameter of pipe

S = Allowable working stress as specified in regulation 343.

C = 0.64 cm(0.25 in).

Maximum Permissible Working Stress for Carbon and Alloy Cast Steel Pipes (See Regulation 351)

Lower value obtained in each case at the specified temperature calculated on the following basis:-

For service temperature at or   T.S.             Et
                                          or
below 454°C (850°F)             2.7             1.5

For service temperature  Et         Sr
                             or           or     Sc
above 454°C (850°F)    1.5         1.5

Amendments found

Machine-assisted list from the amending notifications (DPIIT copies; 1990–1998 from scanned Gazette issues on India Code); may be incomplete.

DateNotificationPartActionWhat changed (summary)Web edition
1993-10-08G.S.R. 516 OCR of scanTable 4SubstitutedChanges the safety factors on T.S., Et, Sr and Sc in Table 4 from 3.5/1.6/1.6/1.6 to 2.7/1.5/1.5/1.5.
Uncertain: Formula layout garbled in OCR.
listed before the capture

Possible IBR 2026 successors (heading match, unverified): Reg. 249, Reg. 250, Reg. 256, Reg. 257, Reg. 258, Reg. 259, Reg. 378