Indian Boiler Regulations, 2026 · Chapter 9 · Safety of Persons inside Boilers

Regulation 333. Safety of persons working inside boilers

Official text — not yet verifiedGazette 1 Oct 2026 · printed pp. 730–731

Not yet checked against the official Gazette; verify before relying on it.

Reproduced from the Gazette of India · verification status above

333.Safety of persons working inside boilers.─ (1) The owner or person in charge shall not compel or allow any person to go inside a steam boiler for any purpose whatsoever unless the boiler is effectively disconnected from any steam or hot water communication with any other boiler, in the manner provided in this regulation.

(2)(a) Effective disconnection shall be made either by the removal of the boiler stop valve or of a length of piping from all steam and hot water connection with any other boiler, vessel or pipe containing steam or hot water by the insertion of substantial blank flanges between the boiler stop valves and piping.

(b)The shutting of a stop valve, stop cock or automatic isolating valve shall not be deemed to compliance with this regulation.

(c)In the case of welded pipe work, however, if a vent pipe of not less than 50 mm internal diameter (bore) is fitted between the main stop valve and the intermediate stop valve on the steam main and between the feed check valve and intermediate check valve on the feed line, this regulation shall be considered to have been complied with, provided such vent pipes are fitted with bolted-on blank flanges and the flanges are removed so as to effectively discharge any leakage steam or water to the atmosphere which the valves on either side of it have been closed.

(3)The owner of a boiler to which this regulation is applicable shall obtain the approval of the Chief Inspector in writing to the method of disconnection which he proposes to use and shall be responsible for ensuring that the method so approved is followed in practice.

(4)When electric light is used for work inside a boiler shell or drum or any confined space within a boiler, the voltage shall not exceed 24 volts and the owner of the boiler shall provide a hand lamp with lamp-guard, keyless socket, insulated handle and extension cord of approved type.

(5)Where power is used for working any equipment inside a boiler the metallic portion of the equipment shall be effectively earthed.

Independent explanation — not the law · draft · engineer review in progress

In short

Nobody may be sent or allowed inside a steam boiler unless it is effectively disconnected from every other boiler or line containing steam or hot water. This duty is on the owner or person in charge.

What "effectively disconnected" means here

  • Remove the boiler stop valve or a length of pipe, or insert substantial blank flanges between the stop valves and the piping.
  • Closing a valve is not enough. A shut stop valve, stop cock or automatic isolating valve does not count.
  • For welded pipework, there is an alternative: vent pipes of at least 50 mm bore between the main and intermediate stop valves (steam) and between the feed check and intermediate check valves (feed). Their bolted blank flanges must be removed, so any leakage vents to atmosphere.
  • The owner needs the Chief Inspector's written approval of the disconnection method and must make sure it is followed.
  • Electric light inside the boiler: 24 V maximum, with a guarded hand lamp as specified.

This is a life-safety provision. Treat the text on the Gazette page as the minimum and follow your site's permit-to-work system too.

Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.

Original drawings for this regulation

Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).

Orientation hints (unverified)

These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.

Historical 1950-edition reg.Heading as OCR'dHeading similaritySource image
396Safety of persons working inside boilers100%Chapter IX-A (DPIIT scan), image 1
IBR 1950 regulation 396 as last published in the DPIIT web edition (archived 2017)

Unofficial archived copy, not verified; see the regulation 396 page for its amendments.

  [image] [image]


Message from
Chairman of Central Boilers Board
•
About Central Boilers
Board
•
History of Indian Boiler Regulations
•
Foreword
•
Contents Chapter
Wise
•
Contents Regulation
Wise
•
List of Amendments
•
Indian Boilers
Act 1923
•
Ibr Forms
•
Home
•
Search
•
Help
•
Contact Us

[image]

[image]

Reg 396

 SAFETY OF PERSONS INSIDE BOILERS

(a)     No person shall be compelled or allowed, by the owner or person in charge, to go inside a steam boiler for any purpose whatsoever unless the boiler is effectively disconnected in the manner hereinafter prescribed from any steam or hot water communication with any other boiler.

Where power is used for working any equipment inside a boiler the metallic portion of the equipment shall be effectively earthed.

(b)     Effective disconnection shall be made either by the removal of the boiler stop valve or of a length of piping from all stream and hot water connections with any other boiler, vessel or pipe containing steam or hot water or by the insertion of substantial blank flanges between the boiler stop valves and piping. The shutting of a stop valve, stop cock or automatic isolating valve alone shall not be deemed to constitute compliance with this Regulation. In the case of welded pipe work, however, if a vent pipe of not less than 2” internal diameter (bore) is fitted between the main stop valve and the intermediate stop valve on the feed line, this Regulation shall be considered to have been complied with, provided such vent pipes are fitted with bolted-on blank flanges and the flanges are removed so as to effectively discharge any leakage steam or water to the atmosphere when the valves on either side of its have been closed.

(c)     The owner of a boiler to which this Regulation is applicable shall obtain the approval of the Chief Inspector in writing to the method of disconnection which he proposes to use and shall be responsible for ensuring that the method of disconnection which he proposes to use and shall be responsible for ensuring that the method so approved is followed in practice.

(d)     When electric light is used for work inside a boiler shell or drum or any confined space within a boiler, the voltage shall not exceed 24 volts and the owner of the boiler shall provide a hand lamp with lamp-guard, keyless socket, insulated handle and extension cord of approved type.

[image] [image]
[image] [image] [image]
Message from Chairman of Central Boilers Board • About Central Boiler Board • History of Indian Boiler Regulations • Foreword • Contents Chapter Wise • Contents Regulation Wise • List of Amendments
• Indian Boilers Act 1923 • Ibr Forms • Home • Search • Help • Contact Us

Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.

Instrument
Indian Boiler Regulations, 2026 (made by the Central Boilers Board under s.40 of the Boilers Act, 2025)
Notification
F.No. P-30014/3/2021-Boiler dated 7 Aug 2026
Published
Gazette of India, Extraordinary, Part III Sec. 4, No. 596, 1 Oct 2026 (CG-DL-E-06102026-276813)
In force
1 Oct 2026 (reg. 1(3): date of publication in the Official Gazette)
Printed Gazette page
730–731
PDF page index
730–731 · open official e-Gazette PDF
Extraction
pdftotext layout mode, sequential regulation detector · text hash d8a9b7e4bb0e1754
Verification
Official text — not yet verified
Amendments checked
None known after 1 Oct 2026 as of build date (not a guarantee). Amendment log
How to cite

Indian Boiler Regulations, 2026, reg. 333, Regulation 333, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.730–731. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).

The citation refers to the government publication. Cite the Gazette, not this website.

Help improve this page

Engineers like you keep IBRsource accurate. Every checked correction or tip helps the next reader.