Effective disconnection before entering a boiler — regulation 333

Two panels: (A) physical disconnection by removing the stop valve or a length of pipe and fitting substantial blank flanges, per reg. 333(2)(a); (B) for welded pipework, two closed valves in series on the steam main and on the feed line with a vent pipe of at least 50 mm bore between each pair, its blank flange removed so leakage discharges to atmosphere, per 333(2)(c). Closing a valve alone does not comply (333(2)(b)); fuel mains are also to be disconnected (Boilers Act 2025 s. 29(c)).
Download
SVG — vector, for screens · PNG — image · PDF — print
Related provisions
The small IBRsource.com mark sits on its own layer (DXF) or group (SVG) and can be deleted. The CC BY 4.0 attribution requirement still applies if you remove it.
Educational drawing, not an approved or fabrication-ready design; verify against the Gazette (report a problem).