Over pressure of Safety Valves
The safety valves shall be so designed that they attain rated discharge capacity with the over pressure not greater than that given in regulation 292; provided that the safety valves which have a discharge area less than 80% of the flow area, the over pressure at which the design lift is attained shall not exceed 10% of the set pressure. For safety valves having discharge area 80% or more of the flow area, the over pressure at which the design lift is attained shall not exceed 5% of the set pressure.