Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)
Regulation 296 — Attachment to Boiler
Text in the DPIIT web edition
Archived copy captured 03 Aug 2022 (Wayback Machine); the same page also prints regulations 294, 295. The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.
| Reg. 294, Reg. 295, Reg. 296 | |||||||
Reg. 295 Pressure Drop
Reg. 296 Attachment to Boiler
|
Earlier text: the 2008 DIPP web edition
Attachment to Boiler
a)Safety Valves shall be mounted, without any intervening valve, on pads or branches used for no other purpose. The axis of the valve shall be vertical. The crosssectional area of the bore of each pad or branch shall be at least equal to the area of the bore at the inlet of the safety valve, or where two or more safety valves are mounted on the same pad or branch, at least equal to the sum of the areas of the inlet bores of all the safety valves.
b)Branches shall be as short as possible so as not to impair the proper action of the safety valves or impose any undue stress on the branches at their point of attachment to the safety valve. Branches, particularly when full lift safety valves are mounted on them, should be radiused at the inlet. The inlet and outlet flanges shall be drilled in accordance with the approximate for the diameter of flanges adopted.