Reg. 295 Pressure Drop
Reg. 296 Attachment to Boiler
|
Earlier text: the 2008 DIPP web edition
Pressure Drop
The safety valves shall be reset at a pressure at least 2.5% below, but not more than 5% below the safety valve set pressure. The 5% limit is increased to 10% for valves having a body seat bore less than 32 mm and/or having a set pressure of 2 bar gauge or less.