Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)
Regulation 292 — Definition
Text in the DPIIT web edition
Archived copy captured 03 Aug 2022 (Wayback Machine); the same page also prints regulation 291. The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.
| Reg. 291, Reg. 292 | |||||||||
Reg. 292
| |||||||||
Earlier text: the 2008 DIPP web edition
Definition
a)Ordinary lift safety valve: A safety valve in which the valve head lifts automatically a distance of at least D/24 with an over-pressure not exceeding 10% of the set pressure. There shall not be any mechanical stop which would prevent the valve head from being lifted a distance of at least D/8. D is the minimum bore of the Body seat.
b)High lift safety valve: A safety valve in which the valve head lifts automatically a distance of at least D/12 with an over pressure not exceeding 10% of the set pressure. There shall not be any mechanical stop which would prevent the valve head from being lifted a distance of at least D/8. D is the minimum bore of the Body seat.
c)Full lift safety valve: A safety valve in which the valve head lifts automatically a distance such that the area of discharge which limits the flow through the valve is between 100% and 80% of the minimum area at any section at or below in body seat. This lift is achieved by a rapid opening within an over pressure not exceeding 5% of the set pressure.