BETAIndependent engineering reference. Source-text verification is ongoing.Verification ongoing.Verification status →
IBRsourceIndian Boiler Regulations, made clear

Indian Boiler Regulations, 2026 · Chapter 15 · Feed Water for Boiler

Regulation 558. Sampling

Official text — not yet verifiedGazette 1 Oct 2026 · printed p. 859

Not yet checked against the official Gazette; verify before relying on it.

Reproduced from the Gazette of India · verification status above

558. Sampling.─ Sampling shall be done by following general directions mentioned in Part-2 of IS: 3025 issued by Bureau of Indian Standards and in particular, the following points shall be observed, namely:-

(a)A stainless steel or monel metal coil shall be fitted on the sampling cock so that the temperature of the water sample shall be well below the boiling point at atmospheric pressure and there is no risk of aeration and concentration due to flashing into steam; and

(b)Samples of feed water shall be collected from the delivery of the boiler feed pump, samples of boiler water from the top drum, and samples of condensate from the delivery of the condensate extraction pump.

Independent explanation — not the law · draft · engineer review in progress

In short

Water samples are taken following the general directions in Part-2 of IS: 3025 issued by the Bureau of Indian Standards, plus two specific points on cooling and sampling locations.

Key points

  • (a) A stainless steel or monel metal coil is fitted on the sampling cock. It keeps the sample temperature well below boiling point at atmospheric pressure, so there is no risk of aeration and concentration from flashing into steam.
  • (b) Sampling points:
  • feed water: from the delivery of the boiler feed pump;
  • boiler water: from the top drum;
  • condensate: from the delivery of the condensate extraction pump.

Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.

Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).

Orientation hints (unverified)

These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.

No candidate heading found in the historical print edition.

Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.

Instrument
Indian Boiler Regulations, 2026 (made by the Central Boilers Board under s.40 of the Boilers Act, 2025)
Notification
F.No. P-30014/3/2021-Boiler dated 7 Aug 2026
Published
Gazette of India, Extraordinary, Part III Sec. 4, No. 596, 1 Oct 2026 (CG-DL-E-06102026-276813)
In force
1 Oct 2026 (reg. 1(3): date of publication in the Official Gazette)
Printed Gazette page
859
PDF page index
859 · open official e-Gazette PDF
Extraction
pdftotext layout mode, sequential regulation detector · text hash f408269d954992b5
Verification
Official text — not yet verified
Amendments checked
None known after 1 Oct 2026 as of build date (not a guarantee). Amendment log
How to cite

Indian Boiler Regulations, 2026, reg. 558, Regulation 558, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.859. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).

The citation refers to the government publication. Cite the Gazette, not this website.

Help improve this page

Engineers like you keep IBRsource accurate. Every checked correction or tip helps the next reader.