Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)
Regulation 625 — Sampling
Text in the DPIIT web edition
Archived copy captured 05 Aug 2022 (Wayback Machine); the same page also prints regulations 623, 624. The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.
| Reg. 623, Reg. 624, Reg. 625 | |||||||||||
Reg. 624 Requirements
Reg. 625 Sampling Sampling shall be done following general directions given in 2 of IS:3025-1964*. In particular, the following points shall be observed :
| |||||||||||
Earlier text: the 2008 DIPP web edition
Sampling
Sampling shall be done following general directions given in 2 of IS:3025-1964*. In particular, the following points shall be observed :
a)It is necessary that a stainless steel or monel metal coil is fitted on the sampling cock so that the temperature of the water sample will be well below the boiling point at atmospheric pressure and there is no risk of aeration and concentration due to flashing into steam; and
b)Samples of feed water shall be collected from the delivery of the boiler feed pump, samples of boiler water from the top drum, and samples of condensate from the delivery of the condensate extraction pump.