Regulation 585A — Stays for fire-boxes and circular furnaces
Text in the DPIIT web edition
Archived copy captured 03 Aug 2022 (Wayback Machine); the same page also prints regulations 586, 585B. The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.
| Reg. 585 a, Reg. 585 b, Reg. 586 | |||||||||||||||||
Reg. 585 b Circumferential stays for circular furnaces and fire-boxes
Reg. 586 Fire-box Crown stays for Loco-type Boilers
| |||||||||||||||||
Earlier text: the 2008 DIPP web edition
Stays for fire-boxes and circular furnaces
(a)Solid screwed stays
For screw stays to combustion chambers and fire-boxes and for longitudinal and cross stays, the maximum working pressure for the stays is to be calculated from the appropriate one of the following two formulae:-
C ¹·²⁸
WP= (D - ------------)² Equation XII/19
A N
C x D1²
WP= Equation XII/20
A
WP is the working pressure in pounds per square inch.
D is diameter of stays over threads in inches.
D1 is diameter of body of stay at its smallest part in inches.
N is number of threads of stay per inch.
A is area in square inches supported by one stay for area to be supported by stays near tubes in fire-box tube plates of Loco-type boilers, [see Regulation 193(a)].
C=7,100 for steel or special wrought iron screw stays to combustion chamber or fireboxes,
C=8,640 for steel longitudinal or cross stays fitted with nuts. =4,700 for copper stays.
Where stays are made with enlarged ends and the body of the stay is smaller in diameter than at the bottom of the thread the working pressure shall be calculated from the second formula.