Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)
Regulation 579 — Plain tubes
Text in the DPIIT web edition
Archived copy captured 03 Aug 2022 (Wayback Machine); the same page also prints regulations 578, 579A, 579B. The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.
| Reg. 578, Reg. 579 A, Reg. 579 B | ||||||||||
Reg. 579 Plain tubes (a) Attachment
| ||||||||||
Earlier text: the 2008 DIPP web edition
Plain tubes
(a)Attachment
Plain tubes may be welded at both ends, welded at the inlet end and expanded at the outlet end, or expanded at both ends.
Where the tubes are expanded only, the process shall be carried out with expanders having parallel rollers, and the expanded portion of the tube shall be parallel through the full thickness of the tube plate. In addition to expanding tubes may be bell-mouthed or beaded at the inlet end.
Where the tube is welded to the tube plate, the tube should be lightly expanded to grip the tube hole before welding.
(b)The thickness of tubes under external pressure shall be calculated as under:-
WP' .D
t = + C Equation XII/14
1.6f
Where,
t = minimum thickness of tube in mm.
WP' =External working pressure in kg/cm²(g)
D = Outside tube diameter in millimetres
C = Corrosion allowance to be taken as 0.75 millimetre but for
Stainless steel C=0.
Higher value may be adopted if desired by user;
F = allowable stress as per regulation 338.
Amendments found
Machine-assisted list from the amending notifications (DPIIT copies; 1990–1998 from scanned Gazette issues on India Code); may be incomplete.
| Date | Notification | Part | Action | What changed (summary) | Web edition |
|---|---|---|---|---|---|
| 1994-02-07 | G.S.R. 107 OCR of scan | (b) | Substituted | Replaces the formula for thickness of tubes under external pressure, with corrosion allowance 0.75 mm (nil for stainless) and stress per regulation 338. Uncertain: Operative words OCR'd 'sub-regulations ill) and tel' read as (b) and (c). | listed before the capture |
| 1994-02-07 | G.S.R. 107 OCR of scan | (c) | Substituted | Replaces the minimum thickness table for straight tubes under external pressure by outside diameter. Uncertain: Table corrected by corrigendum G.S.R. 223. | listed before the capture |
| 1994-02-07 | G.S.R. 107 OCR of scan | (d) | Substituted | Sets the formula and minimum thickness table for straight tubes under internal pressure. Uncertain: Printed with the substituted text although operative words mention only (b) and (c); label OCR'd as '(it)'. | listed before the capture |
| 1994-04-29 | G.S.R. 223 OCR of scan | (c) | Changed | Omits 'not' (p.331, col. 2, line 29), in the 'In no case ... shall not be less' sentence. Uncertain: Mapping to 579(c) inferred. | listed before the capture |
| 1994-04-29 | G.S.R. 223 OCR of scan | (c) table | Changed | Replaces row 'Exceeding 51 but not exceeding 77 3.38' with rows 51-70 mm 3.12 and 70-77 mm 3.38. | listed before the capture |
| 1994-04-29 | G.S.R. 223 OCR of scan | (c) table | Changed | Corrects '1.02' to '102' in the diameter column (p.331, col. 2, line 38). | listed before the capture |
| 1994-04-29 | G.S.R. 223 OCR of scan | (d) formula | Changed | Corrects the denominator of the internal-pressure equation to read '2f' (p.331, col. 2, line 42). Uncertain: Wrong text OCR'd as '21'. | listed before the capture |
| 1994-04-29 | G.S.R. 223 OCR of scan | (d) | Changed | Omits a word (OCR 'flc't', probably 'not') at p.331, col. 2, line 47. Uncertain: Word garbled; mapping inferred. | listed before the capture |
| 1994-04-29 | G.S.R. 223 OCR of scan | (d) table | Changed | Omits 'the' at p.331, col. 2, line 49 (likely the table heading 'the thickness (mm)'). Uncertain: Mapping inferred. | listed before the capture |