Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)
Regulation 577 — Flat tube plates and tube nests
Text in the DPIIT web edition
Archived copy captured 03 Aug 2022 (Wayback Machine); the same page also prints regulations 575, 576, 577A, 577B. The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.
| Reg. 575, Reg. 576, Reg. 577 a, Reg. 577 b
| ||||||||||||||||||
Reg. 576 Wide water spaces between and around tube nests
Reg. 577 Flat tube plates and tube nests a) Stay tubes and plain tubes
Reg. 577 b Parts of flat plates within tube nests
| ||||||||||||||||||
Earlier text: the 2008 DIPP web edition
Flat tube plates and tube nests
a)Stay tubes and plain tubes
(i)Stay tubes are tubes having a weld depth equal to the nominal tube thickness plus 3 mm as shown typically in figures XII/68A(i) to (iv). These stay tubes are not required within tube nests except when the tube nests comprise tubes which are expanded only as shown typically in figure XII/67A (iii).
(ii)If tube nests comprise plain tubes which are expanded and beaded, expanded and belled as shown typically in figure XII/67A(iv) or expanded and welded (as shown typically in Figs. XII/67A (i) and (ii) ), welded stay tubes (as shown typically in Figs. XII/67A (i) to (iv) shall be used in boundary rows in sufficient numbers to carry the flat plate loadings outside the tube area.
(iii)For plain tube and stay tubes exposed to flame or gas temperatures exceeding 600° C, the ends of welded tubes shall be dressed flush with the welds and the ends of the expended tubes shall be as shown in figures XII/67A(iii) and (iv). If not so exposed, the ends of welded tubes shall extended a maximum of 10 mm beyond the weld or, in the case of expanded tubes, the tubes shall project beyond the tube plate up to a maximum of 15 mm.
(iv)Each stay tube shall be designed to carry its due proportion for the load on the plates which it supports. The thickness of stay tubes welded into tube plates shall be such that the axial stress on the thinnest part of the tube does not exceed 70 N/mm².
Amendments found
Machine-assisted list from the amending notifications (DPIIT copies; 1990–1998 from scanned Gazette issues on India Code); may be incomplete.
| Date | Notification | Part | Action | What changed (summary) | Web edition |
|---|---|---|---|---|---|
| 1996-12-06 | G.S.R. 59 OCR of scan | Substituted | Replaces regulation 577 on flat tube plates and tube nests: stay tubes, plain tubes, tube end projection and stress limits. | listed before the capture |
Possible IBR 2026 successors (heading match, unverified): Reg. 91, Reg. 92, Reg. 575