Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)
Regulation 48 — Material
Text in the DPIIT web edition
Archived copy captured 03 Aug 2022 (Wayback Machine). The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.
| Reg. 48 MATERIALS OF CONSTRUCTION SEAMLESS FERRITIC AND AUSTENITIC ALLOY STEEL BOILER, SUPERHEATER AND HEAT EXCHANGER TUBES |
| (a) Material. - (i) The tubes shall be seamless and manufactured from steel produced by an open hearth or electric process or any of the oxygen processes. The steel shall be fully killed. (ii) The steel shall conform to the limits of chemical compositions given in Table-1 and 2. (iii) The grain size of cold worked grade TP 321H shall be No.7 or coarser. (b) Heat treatment. - (i) All tubes of grades in Table-1, except T 91, 12X1Mo and X20CrMoV121 shall be reheated and furnished in full annealed, isothermal annealed or normalised and tempered condition. If furnished in the normalised and tempered condition, the minimum tempering temperature for Grades T1 and T11 shall be 650 degree C and the minimum tempering temperature for Grades T5, T9 and T22 shall be 675 Degree C. (ii) Tubing of Grades T1, T2 and T12 either hot finished or cold drawn, may be given a final heat treatment at 650 degree C to 730 degree C, instead of heat treatments specified in sub-clause (i) above, at the option of the manufacture. (iii) Grade T91 shall be normalised at 1040 degree C minimum and tempered at 730 degree C minimum as a final heat treatment. (iv) Grade 12x1Mo shall be normalised at 950 - 980 degree C and tempered at 720 - 750 degree C for a period of 1 to 3 hours. (v) Grade X20CrMoV121 shall be normalised at 1020 - 1070 degree C and tempered at 730 - 780 degree C for a period of 1 hour minimum. (vi) All austenitic tubes (Table 2) shall be furnished in the heat treated condition. The heat treatment procedure, except for the H grades shall consist of heating the material to a minimum temperature of 1040 degree C and quenching in water or rapidly cooling by other means. (vii) All H grades shall be furnished in the solution treated condition. If cold working is involved in processing, the minimum solution treating temperatures for grades TP321H and TP347H shall be 1100 degree C and for grades TP304H and TP316H shall be 1040 degree C. If the P grade is hot rolled, the minimum solution treatment for grades TP 321 H and TP 347 H shall be 1050 degree C and for grades TP 304H and TP 316H shall be 1040 degree C. (c) Workmanship and tolerance - The tubes shall be well finished, cleaned free from harmful defects. They shall be reasonably straight, smooth, cylindrical and subject to the following tolerances. Finished tubes shall be reasonably straight and have smooth ends free of burrs. They shall have a workmanlike finish. Surface imperfections like any discontinuity or irregularity found in the tube may be removed by grinding, provided that a smooth curved surface is maintained, and the wall thickness is not decreased to less than that permitted. The outside diameter at the point of grinding may be reduced by the amount so removed. (i) Permissible variation in outside diameter: For all grades except 12X1Mf and X20CrMoV121
For grade 12X1Mf
For grade X20CrMoV121
(ii) Permissible variation in Wall Thickness : For all grades except 12X1Mf and X20CrMoV121
For Grade 12X1Mf
For Grade X20CrMoV121
(iii) Permissible variation in length for exact length tubes. For all Grades except 12X1Mf and X20CrMoV121
Note : These permissible variations in lengths apply to cut lengths upto and including 7.3 m. For lengths over 7.3 m, an additional over tolerance of 3 mm for each 3 m or fraction thereof, shall be permissible, upto a maximum of 12 mm. For grade 12X1Mf
For grade X20CrMoV121
(d) Test specimens. - (i)Test specimens required for the flattening and expanding/ flaring test specified in regulations 49(a), 49 (b) and 49(c) shall be taken from the ends of finished tubes prior to upsetting, swaging, expanding or any other forming operations or being cut to length. They shall be smooth on the ends and free from burrs and flaws. (ii) If desirable and practicable, tensile test may be carried out on full section of the tubes upto the capacity of the testing machine. For large size tubes, the tensile test specimen shall consist of strip cut longitudinally from the tube and which is not straightened within the gauge length further heat treated. (iii) If any test specimen shows flaws or defective machining it may be discarded and another specimen substituted. (iv) All specimens shall be tested at room temperature. (e) Number of tests. - The tests specified in regulations 49(a), 49(b) and 49(c) shall be made on minimum 2 tubes for first 100 and 1 per 100 or part thereof for tubes over 100 numbers.
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Earlier text: the 2008 DIPP web edition
MATERIALS OF CONSTRUCTION
SEAMLESS MOLYBDENUM STEEL BOILER AND SUPERHEATER TUBES FOR DESIGN METAL TEMPERATURES NOT EXCEEDING 510 DEGREE C (950 DEGREE F).
(a)Material - The tubes shall be manufactured from steel produced by the Open Hearth or Electric process or any of the oxygen processes and shall conform to the following limits of chemical composition:-
Chemical Composition (ladle analysis)
Carbon 0.20% maximum Silicon 0.10 to 0.45% Manganese 0.35 to 0.80% Phosphorus 0.05% maximum Sulphur 0.05% maximum Molybdenum 0.25% to 0.65%
The steelmaker shall prove to the satisfaction of the Inspecting Authority that the quality of the steel is of the required high temperature creep strength.
(b)Heat Treatment - The tubes shall be fully annealed or normalized and tempered at a temperature approved by the Inspecting Authority.
(c)Workmanship and tolerance - The tubes shall be well finished, clean and free from harmful defects. They shall be reasonably straight, smooth, cylindrical and subject to the following tolerances before bending:-
Diameter.- The external diameter of the tubes measured at any point shall be within the
(i)following tolerances of the diameter specified:-
Type of Tube Outside Diameter of Tube Tolerance
Over 30 ft Upto and including 63.5 mm + 0.4 mm
Hot finished - 0.8 mm
------------------------------- ------------------
Over 63.5 mm ± 1%
Cold drawn All sizes + 0%
- 1%
(ii)Thickness.- The thickness of the tubes shall be within the following tolerances:-
Type of Tube Outside Diameter of Tube Tolerance
Upto and including 2½ inches + 17½%
- 7½%
Hot finished ------------------------------- ------------------
+ 15%
Over 63.5 mm - 5%
Cold drawn All sizes + 10%
- 5%
Where the ends of the tubes are swelled or reduced the thickness at the ends may be decreased below or increased above the nominal thickness of the tubes by an amount in proportion to the percentage of such swelling or reduction and, in addition to this allowance, the tolerances relating to thickness shall also apply. Swelling or reduction shall be carried out before the heat treatment specified in Regulation 48(b).
(iii)Length.- The tubes shall be not less than the nominal length but may exceed it by the amount given below:-
Upto and including 30 ft 1/8 inch Over 30 ft ¼ inch
(d)Selection of tubes for testing - After heat treatment the tubes shall be presented for mechanical testing in accordance with regulations 49(a), 49(b) and 49(c) in batches of not more than 100 of the same nominal diameter and thickness. The manufacturer shall provide at his own expense extra tube at the rate of 2 per cent of each diameter and thickness of tubes specified and the Inspecting Officer shall select for test such of the tubes as he may think proper to the extent of the percentage mentioned. Should the number of tubes ordered of any one nominal size exceed 400 then, for every 100 tubes or part thereof above that number, one additional tube shall be provided. The samples for testing shall not be heat treated after selection.
Selection of specimens for testing may be in accordance with any other standard code in which case the code adopted shall be specified.
Amendments found
Machine-assisted list from the amending notifications (DPIIT copies; 1990–1998 from scanned Gazette issues on India Code); may be incomplete.
| Date | Notification | Part | Action | What changed (summary) | Web edition |
|---|---|---|---|---|---|
| 2001-04-10 | G.S.R. 219 | Substituted | Replaced as part of the block substitution of regulations 36 to 56 (tube specifications). | listed before the capture | |
| 2004-08-02 | G.S.R. 265 | Substituted | Replaces regulation 48 together with Tables 1 and 2. | listed before the capture |