Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)
Regulation 320 — WATER GAUGES
Text in the DPIIT web edition
Archived copy captured 03 Aug 2022 (Wayback Machine); the same page also prints regulations 317, 318, 319. The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.
| Reg. 317, Reg. 318, Reg. 319, Reg. 320 | ||||||||||||||||||||
Reg. 318 Blow-down Mountings
Reg. 319 Blow-down Valve or Cock
Reg. 320 WATER GAUGES
|
Earlier text: the 2008 DIPP web edition
WATER GAUGES
a)Every boiler shall have two means of indicating the water in it of which one shall be conventional gauge glass:
Provided that in the case of boiler drums below 3 feet (91 cm) diameter where there is difficulty in fitting two water gauges, two test cocks and a glass water gauge shall be fitted.
b)The lowest visible part of the glass of the water gauge and lower test cock shall be fixed at safe working level. For locomotive type and vertical boilers this shall not be less than 50 millimetres above the highest part of the firebox roof plate.
Minimum length of the visible portion of the gauge glasses shall be 200 mm. The length may be increased depending upon the capacity of the boiler by the Chief Inspector/Director of boiler of the manufacturing State.
c)Glass water gauges shall be so placed as to be easily seen and reached by the boiler attendant. The fittings of glass water gauges and test cocks shall be of substantial make with large passage ways through them to facilitate cleaning. The gauge cocks when open shall have their handles in a vertical direction and each handle at its junction with the plug shall be plainly marked with a deep line to indicate the direction of the passage way through the plug. When detachable handle are provided arrangement shall be made to prevent incorrect fitting of the handles.
Amendments found
Machine-assisted list from the amending notifications (DPIIT copies; 1990–1998 from scanned Gazette issues on India Code); may be incomplete.
| Date | Notification | Part | Action | What changed (summary) | Web edition |
|---|---|---|---|---|---|
| 1994-11-23 | G.S.R. 607 OCR of scan | (a) | Substituted | Replaces sub-regulation (a): two means of indicating water level, one a conventional gauge glass, with proviso for drums below 91 cm. | listed before the capture |
| 1994-11-23 | G.S.R. 607 OCR of scan | (b) | Omitted | Omits sub-regulation (b). Uncertain: OCR reads '(N)'. | listed before the capture |
| 1994-11-23 | G.S.R. 607 OCR of scan | (c),(d) | Renumbered | Re-letters sub-regulations (c) and (d) as (b) and (c). Uncertain: OCR reads 'as sub-regulations (b) and (e)'; read as (b) and (c). | listed before the capture |
| 1994-11-23 | G.S.R. 607 OCR of scan | (b) as re-lettered | Amended | Changes "2 inches" to "50 millimetres" and adds a minimum 200 mm visible gauge-glass length. | listed before the capture |
| 2010-10-07 | G.S.R. 821(E) | Amended | Substitutes 'Inspecting Authority' for the manufacturing State's Chief Inspector or Director of Boilers. | listed before the capture |