Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)
Regulation 318 — Blow-down Mountings
Text in the DPIIT web edition
Archived copy captured 03 Aug 2022 (Wayback Machine); the same page also prints regulations 317, 319, 320. The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.
| Reg. 317, Reg. 318, Reg. 319, Reg. 320 | ||||||||||||||||||||
Reg. 318 Blow-down Mountings
Reg. 319 Blow-down Valve or Cock
Reg. 320 WATER GAUGES
|
Earlier text: the 2008 DIPP web edition
Blow-down Mountings
a)Each boiler shall be fitted, with a suitable blow down valve or cock placed at, or as near as practicable, to the lowest point of the boiler.
b)For locomotive, vertical and marine type boilers, the valve or cock shall be
attached direct to the boiler or to a suitable pad or stand pipe. For water tube boilers the valve or cock shall be outside the brickwork with a substantial steel pipe between it and the mudbox.
c)For Cornish and Lancashire boilers the cock or valve may be attached to a cast steel elbow pipe of substantial section bolted to a suitable stand pipe or pad riveted to the boiler. But cast iron elbow pipes shall not be permitted.