Worked example · Reg. 458
Dished end maximum allowable working pressure, Equation (12/7) (regulation 458)
What the regulation requires
Regulation 458(1): for unstayed ends of shells and tops of vertical boilers and the like boiler parts, when dished to partial spherical form, the maximum allowable working pressure is determined by the following formula (printed as a fraction with R below the line):
P = 0.216 S(t−0.79) Equation (12/7)
---------------
R
458(5): when the end has a manhole in it, (t-3.97) is substituted for (t-0.79) in the formula.
458(6): the total depth of flange of manhole from the outer surface measured on the minor axis is at least equal to:
√ (T x W) depth of flange in mm. Equation (12/8)
Symbols and units
As printed:
- P = the maximum allowable working pressure in kg/cm2(g)
- t = the thickness of the end plate in mm, but in no case less than the thickness of the shell to which it is attached
- R = the inner radius of curvature of the end in mm, which shall not exceed the external diameter of the shell to which it is attached
- S = the minimum tensile breaking strength of plate in kg/cm2, or whatever is allowed for it
- T = the thickness of the plate in mm; W = the minor axis of the hole in mm (Equation 12/8)
Worked example
Example values (hypothetical, not from the regulation): S = 4100 kg/cm2; t = 16 mm; R = 1200 mm; shell external diameter 1300 mm; shell thickness 14 mm.
Without a manhole:
- t − 0.79 = 16 − 0.79 = 15.21 mm
- 0.216 × S = 0.216 × 4100 = 885.6 kg/cm2
- 885.6 × 15.21 = 13469.976
- P = 13469.976 / 1200 = 11.22498 kg/cm2(g)
- Result: P = 11.22 kg/cm2(g) (rounded to 2 decimal places).
With a manhole whose minor axis W = 300 mm (example value):
- t − 3.97 = 16 − 3.97 = 12.03 mm
- 885.6 × 12.03 = 10653.768
- P = 10653.768 / 1200 = 8.87814 kg/cm2(g), i.e. 8.88 kg/cm2(g) (2 decimal places)
- Flange depth, Equation (12/8): √(16 × 300) = √4800 = 69.28 mm (2 decimal places), at least.
- 458(7): depth of the crown plate opening not less than twice the plate thickness with a minimum of 25 mm: 2 × 16 = 32 mm, which is more than 25 mm, so 32 mm.
Conditions checked: R = 1200 mm does not exceed the shell external diameter of 1300 mm (458(1) and (2)); t = 16 mm is not less than the shell thickness of 14 mm (458(1)).
Checks and limits
- Applies to ends dished to partial spherical form (458(1)); other end shapes are not covered.
- 458(3) states the inside radius of curvature of the flanges to the shell shall be not less than 4 times the crown plate thickness and in no case less than 63 mm; 458(4) states the inside radius of curvature of flanges shall be not less than twice the crown plate thickness and in no case less than 25 mm. The two sub-regulations give different minimums and the text does not say which flanges each covers; check the Gazette page. They are not calculated here.
- S may be "whatever is allowed for it"; the example does not decide what value is allowed.
- The example does not check the shell, the attachment, or any other part of the boiler.
Educational example only. Not a design calculation; verify against the official Gazette and applicable requirements.
Calculator
Runs in your browser. Results are for learning only; check every input, unit and condition against the official Gazette text of regulation 458.