Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)
Regulation 620 — Extent to which variation from the standard conditions laid down in the preceding Chapters is permissible
Text in the DPIIT web edition
Archived copy captured 05 Aug 2022 (Wayback Machine); the same page also prints regulations 618, 619. The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.
| Reg. 618, Reg. 619, Reg. 620 Small Industrial Boilers General Reg 618 Scope | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Reg. 619 Definition
Reg. 620 Extent to which variation from the standard conditions laid down in the preceding Chapters is permissible.-
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Earlier text: the 2008 DIPP web edition
Extent to which variation from the standard conditions laid down in the preceding Chapters is permissible.-
The following variations from the standard conditions laid down in the preceding Chapters shall be permitted, subject to the conditions specified below, with due regard to the safety of the boilers and personnel.
1)Materials:-
(a)The materials used in the construction of Small Industrial boilers shall, except as otherwise provided hereinafter, conform to the provisions made in Chapter II of these regulations.
(b)Steel plates used in the construction of the boilers shall be of IS: 2062 grade B or C or equivalent and the plate for shell and heads shall be not less than 6 mm. in thickness and the heads as tube sheets for tubes rolled in shall be at least 8 mm. in thickness.
(c)(i) Heads of parts of boilers when not exposed to direct impact of flame may be made of cast iron or malleable iron provided they comply with other requirements of these regulations.
(ii)The allowable stress on cast iron or malleable iron shall be based on the
tensile strength of material with a factor of safety of not less than 4.5.
2)Design, construction, workmanship and the method of computing the maximum allowable working pressure:
(a)(i) The construction except where otherwise specified shall be the same as those prescribed in the relevant provisions of the preceding Chapters of these regulations.
(ii)In the case of fusion welded boiler neither stress relieving nor radiography of welded joints is required.
(b)(i) In the Small Industrial boilers unflanged steel tube plate may be inserted into the shell and welded for the entire thickness as shown in Fig XIV/1 with a fillet weld having a throat not less than 11/4 times the thickness of the shell or tube sheet whichever is smaller.
(ii)The minimum thickness of unflanged welded tube sheets shall be 10 mm.
t1 = 2 times required thickness of a seamless shell but never less than 1.25 ts or greater than t.
(iii)The temperature of the heating element of electrically heated steam boilers shall be so controlled that it shall not exceed 650° C.
(e)(i) The tubes shall be made of steel.
(ii)The tube holes shall be drilled full size with shells butt straps and ends bolted up in position or may be punched at least 13 mm smaller in diameter than full size and then drilled, reamed or finished full size with a rotating cutter. The sharp-edges and chips removed, the plates and butt straps reassembled metal to metal with pins fittings the holes and with tack bolts.
(3)Inspection and testing:-
The Small Industrial Boilers shall be subjected to inspection during construction and after completion by an Inspecting Authority. The inspection of the boilers shall be made at the following stages:
A. Shell type Boilers:
(i)Material identification and inspection.
(ii)Inspection of each component after completing welding and drilling.
(iii)Assembly of boiler.
(iv)Hydraulic test:-
(a)Every completed boiler of riveted construction shall be tested hydraulically at least twice the working pressure;
(b) In case of a boiler wholly or partly welded construction, the hydraulic
test pressure shall be equal to two times the maximum allowable
working pressure of the boiler.
(v)A test coupon shall be provided by the maker for conducting root and face bend tests.
B. Coil type Boilers, once through boilers and water tube boilers:
(i)Identification of materials.
(ii)Hydraulic test: The pressure for hydraulic test shall be two times that of the working pressure of the boiler.
(4)Certificates and Maker’s Stamps.-
(a)The certificate and maker’s stamp shall be in conformity with the provisions of Chapter I of these regulations.
(b)If owing to small size of the boiler all information cannot be visibly stamped on the boiler plate, maker’s certificate accompanying the boiler shall contain the necessary details, but in all cases name, works number and the year of the make must be stamped or exhibited on the boiler.
Amendments found
Machine-assisted list from the amending notifications (DPIIT copies; 1990–1998 from scanned Gazette issues on India Code); may be incomplete.
| Date | Notification | Part | Action | What changed (summary) | Web edition |
|---|---|---|---|---|---|
| 1993-09-21 | G.S.R. 488 OCR of scan | Substituted | Replaces permitted variations: IS 2062 plates and minimum thicknesses, cast-iron heads, no stress relieving/radiography, welded tube plates, inspection stages, 2x hydraulic test, stamping. | listed before the capture |