Reg. 62
MATERIALS OF CONSTRUCTION

Test Specimens

(a) Test specimens required for the flattening and flaring test specified in regulations 59 (a) and 59 (b) shall be taken from the ends of finished tubes prior to up setting, swaging, expanding or other forming operations or being cut to length.  They shall be smooth on the ends and free from burrs and flaws. 

(b) If desirable and practicable, tensile test, may be carried out on full section of the tubes up to the capacity of the testing machine.  For large size tubes, the tensile test specimen shall consist of strip cut longitudinally from the tube and not flattened between the gauge marks and further heat treated. The sides of the specimen shall be parallel between gauge marks.             

(c) All specimens shall be tested at room temperature.

 

Earlier text: the 2008 DIPP web edition

MATERIALS OF CONSTRUCTION

ELECTRICAL -RESISTR|ANCE -WELED STEEL BIOLER AND SUPER-HEATER TUBES FOR DESIGN METAL TEMPERATURES NOT EXCEEDING 454⁰ C (850⁰ F)

Test Specimens

(a)Test specimens required for the flattening and flaring test specified in regulations 59 (a) and 59 (b) shall be taken from the ends of finished tubes prior to up setting, swaging, expanding or other forming operations or being cut to length. They shall be smooth on the ends and free from burrs and flaws.

(b)If desirable and practicable, tensile test, may be carried out on full section of the tubes up to the capacity of the testing machine. For large size tubes, the tensile test specimen shall consist of strip cut longitudinally from the tube and not flattened between the gauge marks and further heat treated. The sides of the specimen shall be parallel between gauge marks.

(c)All specimens shall be tested at room temperature.

Amendments found

Machine-assisted list from the amending notifications (DPIIT copies; 1990–1998 from scanned Gazette issues on India Code); may be incomplete.

DateNotificationPartActionWhat changed (summary)Web edition
1999-10-14G.S.R. 345SubstitutedReplaced as part of the block substitution of regulations 57 to 63A (electrically welded tubes).listed before the capture