Regulation 59 — Flattening test

Unofficial DPIIT web edition · not verified1 amendment found

Text in the DPIIT web edition

Archived copy captured 03 Aug 2022 (Wayback Machine). The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.

Unofficial DPIIT web edition · archived 2022 · not checked against the Gazette
Reg. 59
MATERIALS OF CONSTRUCTION
 

(a) Flattening test.- (i) A section of the tube not less than 40 mm length shall be flattened cold between parallel plates.  No cracks or breaks in the metal shall occur until the distance between the plates is less than the given by the following formula.  Evidence of lamination or burnt material or incomplete penetration of the weld shall not develop during the testing.

             ( 1 + e ) t
H = ----------------
             e + ( t /D )

Where                    t  =  Specified thickness of tube (in mm)

                                D = Specified outside diameter of tube (in mm)

                                e = Flattening test constant as given below :

                                0.10 for tube grade WC 1

                                0.07 for tube grades WC2 & WC3.

(ii)           The weld shall be placed 90 degree from the line of direction of the applied force.

(iii)               Superficial rupture as a result of minor surface imperfections shall not be cause for rejection.

(iv)               Flattening test carried out in accordance with any other standard code may be accepted in which case the code adopted shall be specified.

(b) Flaring Test.- A section of tube of length equal to 1.5 times the outside diameter, but not less than 50 mm, shall stand being flared with a tool having 60 or 45 degree included angle until the tube at the mouth of the flare has expanded to the percentage given below without cracking

_________________________________________________________________________
Tube                                        % expansion in outside diameter D for a d/D of_______

Grade                                      0.6 and            Over 0.6 to             Over 0.8

under               0.8 including_____________________

WC 1                                          12                         15                         19

WC2                                           12                         15                         19

WC3                                           10                         12                         17

_________________________________________________________________
d = inside diameter of tube.

 

Earlier text: the 2008 DIPP web edition

MATERIALS OF CONSTRUCTION

ELECTRICAL -RESISTR|ANCE -WELED STEEL BIOLER AND SUPER-HEATER TUBES FOR DESIGN METAL TEMPERATURES NOT EXCEEDING 454⁰ C (850⁰ F)

Flattening test

(a)Flattening test.- (i) A section of the tube not less than 40 mm length shall be flattened cold between parallel plates. No cracks or breaks in the metal shall occur until the distance between the plates is less than the given by the following formula. Evidence of lamination or burnt material or incomplete penetration of the weld shall not develop during the testing.

 ( 1 + e ) t
 H = ----------------
 e + ( t /D )
Where t =     Specified thickness of tube (in mm)
              D = Specified outside diameter of tube (in mm)
              e = Flattening test constant as given below :
              0.10 for tube grade WC 1
              0.07 for tube grades WC2 & WC3.

(ii)The weld shall be placed 90 degree from the line of direction of the applied force.

(iii)Superficial rupture as a result of minor surface imperfections shall not be cause for rejection.

(iv)Flattening test carried out in accordance with any other standard code may be accepted in which case the code adopted shall be specified.

(b)Flaring Test.- A section of tube of length equal to 1.5 times the outside diameter, but not less than 50 mm, shall stand being flared with a tool having 60 or 45 degree included angle until the tube at the mouth of the flare has expanded to the percentage given below without cracking

Tube Grade                    % expansion in outside diameter D for a d/D of
                              0.6 and        Over 0.6 to          Over 0.8
                              under          0.8 including

WC1                           12             15                   19
WC1                           12             15                   19
WC3                           10             12                   17

d = inside diameter of tube.