Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)
Regulation 591D — Anchor plates angles, link pins and the like members
Text in the DPIIT web edition
Archived copy captured 03 Aug 2022 (Wayback Machine); the same page also prints regulations 591C, 591E. This page was revised after the 2019 capture, so later amendments may be included. Units as printed.
| [image] | [image] |
| ||||||||||||||||||||||||||||||||||||||||||||||||||
Earlier text: the 2008 DIPP web edition
Anchor plates angles, link pins and the like members
The strength of anchor plates, angles and link pins calculated at the weakest section shall be as follows:-
(i)Link pins shall be so designed that the shear stress does not exceed 8,000 pounds per square inch, the strength of pins in double shear being taken as 1.875 times the strength of pins in single shear.
(ii)Anchor plates or angles shall be so designed that the calculated stress does not exceed one-seventh of the minimum tensile stress of the material used, but in no case shall the thickness be less than seven-eighth of the thickness of the shell plate with a minimum of ½ inch, nor the length of the portion attached to the end plate be less than the distance between the lines of end to shell flat margin and the breathing space line around the flues or tube nests.