Reg. 569 Hemispherical crowns
Reg. 570 Manholes and other openings in shells
| |||||||||
Earlier text: the 2008 DIPP web edition
Hemispherical crowns
The maximum working pressure for hemispherical crowns subjected to internal pressure shall be determined by the following formula:-
(t-2) S x C
WP = Equation XII/9
R
Where,
t is thickness of plate in thirty-seconds of an inch.
WP is the working pressure in pounds per square inch.
R is inner radius of curvature in inches.
S is minimum tensile strength of the plate in tons per square inch.
C is a constant, as given below.
In no case, however, shall the factor of safety of the crown plate be less than 4 nor the plate thickness be less than specified in Table given under Regulation 563.
C=32 where Class I requirements are complied with.
C=27 where Class II requirements are complied with.
C=23 for Class III boilers when stress relieved.
C=21 for Class III boilers when not stress relieved.