Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)
Regulation 565 — Horizontal shelves of tube plates forming part of the shell
Text in the DPIIT web edition
Archived copy captured 03 Aug 2022 (Wayback Machine); the same page also prints regulation 566. The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.
| Reg. 565, Reg. 566 | |||||||||||||||||||||||||||
Reg. 566 Dished end plates for Lancashire and Cornish boilers
| |||||||||||||||||||||||||||
Earlier text: the 2008 DIPP web edition
Horizontal shelves of tube plates forming part of the shell.-
The number of gussets required to support the horizontal shelves of tube plates to withstand the vertical load due to the pressure on the boiler ends shall be determined in the following manner:-
For combustion chamber tube plates the minimum number of the gussets shall be:-
Where C exceeds 4560 1 gusset. Where C exceeds 6240 2 gussets. Where C exceeds 7440 3 gussets.
For the smoke fox tube plate the minimum number of gussets shall be:-
Where C exceeds 4560 1 gusset.
Where C exceeds 8400 2 gussets.
PAD
C =
t Equation XII/4
where,
A is maximum horizontal dimension of the shell from the inside of the shell plate is to the outside of the tube plate in inches (see Fig.XII/61) .
D is inside diameter of the boiler in inches.
P is working pressure in pounds per square inch t is thickness of tube plate in thirty seconds of an inch.
The shell plates to which the sides of the tube plates are connected shall be not less than 1/16 inch thicker than is required by the formula applicable to shell plates with continuous circularity; and where gussets or other stays are not fitted to the shelves, the strength of the parts of the circumferential seams at the top and bottom of these plates from the outside of one tube plate to the outside of the other, shall be sufficient to withstand the whole load on the boiler end, with a factor of safety of not less than 4.5.