Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)
Regulation 553 — Access
Text in the DPIIT web edition
Archived copy captured 03 Aug 2022 (Wayback Machine); the same page also prints regulations 551, 552. The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.
| Reg. 551, Reg. 552, Reg. 553 | |||||||||||||||||||||||||||||||||||||
Reg. 552 Gusset stays
Reg. 553 Access
| |||||||||||||||||||||||||||||||||||||
Earlier text: the 2008 DIPP web edition
Access
At least one manhole or sight hole shall be provided in the upper part of the boiler, the dimensions being not less than those in Table XII/2 for the given size of boiler:-
TABLE XII/2
Dimensions of Manholes or Sight Holes
Minimum size of hole
Diameter of boiler
inches
Boilers not exceeding 2 feet and 6 inches 9 x 7
Boiler over 2 feet and 6 inches diameter and not
12 x 9
exceeding 3 feet
Boiler over 3 feet diameter and not exceeding 3 feet and 6
14 x 10
inches
Boiler over 3 feet and 6 inches diameter and not
15 x 11
exceeding 4 feet
Boiler over 4 feet 16 x 12
Where the size of construction of the boiler does not permit of entry for cleaning or inspection of all internal surfaces, cleaning holes sufficiently large and numerous shall be provided for this purpose. The cleaning holes shall be not less than 3 ½ inches x 2 ½ inches in size.
One cleaning hole shall be provided opposite at least one end of each crosstube in a vertical crosstube boiler. Where the water tubes are arranged in banks, an opening of sufficient size to permit of their replacement shall to be provided.
At the bottom of the narrow water space in vertical boilers where internal access is not possible, mud holes shall be arranged at equal distances round the circumference of the boiler not less in number than as given in Table XII/3.
TABLE XII/3
Number of Lower Cleaning Holes of Mud Holes
Diameter of boiler No. of holes 2 Feet and over but not exceeding 3 feet 3 Over 3 feet and not exceeding 5 feet 4 Over 5 feet and not exceeding 6 feet 5 Over 6 feet and not exceeding 7 feet and 6 inches 6
Over 7 feet and 6 inches and not exceeding 8 feet and 6 inches 7
Over 8 feet and 6 inches and not exceeding 9 feet 8
Cleaning holes or mud holes in loco-type boilers shall be provided at each bottom corner or as nearly as possible in the corners of the outer firebox casing and at the top corners above firehole opening and also at each corner of the saddle plate in line with the bottom of barrel. Smoke box tube plate shall be provided with a mud hole.
A manhole shall be provided in the lower part of front end plates of Lancashire boilers and in similar boilers with internal flues wherever practicable.