Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)
Regulation 526 — Procedure at subsequent inspection
Text in the DPIIT web edition
Archived copy captured 03 Aug 2022 (Wayback Machine); the same page also prints regulations 527, 528. The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.
|
REGULATIONS FOR REGISTRATION AND INSPECTION OF ECONOMISERS AND FEED PIPES | ||||||||||
| ||||||||||
|
REGULATIONS FOR REGISTRATION AND INSPECTION OF ECONOMISERS AND FEED PIPES | ||||||||||
| ||||||||||
|
REGULATIONS FOR REGISTRATION AND INSPECTION OF ECONOMISERS AND FEED PIPES | ||||||||||
|
Earlier text: the 2008 DIPP web edition
STANDARD CONDITIONS FOR THE DESIGN AND CONSTRUCTION OF ECONOMIZER, FEED PIPES, FEED HEATERS AND OTHER SIMILAR VESSELS
REGULATIONS FOR REGISTRATION AND INSPECTION OF ECONOMISERS AND FEED PIPES
Procedure at subsequent inspection
a)After the economiser has been cleaned the Inspector shall make a thorough examination so far as its construction permits. The external condition of the tubes should be carefully noted for wasting especially at the feed inlet end and all accessible tubes should be calibered. The internal surfaces of cast iron tubes should be closely observed for graphitic wasting as far as it is possible and in the event of any tube failure these should be broken up for scrutiny so that the general internal condition of the other tubes may be estimated.
b)Where tubes or other parts are wasted, the strength should be recalculated.
c)The scraper gear should be examined to note if any parts are missing if the length of travel is adequate and if the scrapers are correctly adjusted.
d)All cap bolts are to be inspected, also the condition and position of the dampers and baffles.
e)The record of each inspection and calculations will be entered in the Memorandum of Inspection Book.
Amendments found
Machine-assisted list from the amending notifications (DPIIT copies; 1990–1998 from scanned Gazette issues on India Code); may be incomplete.
| Date | Notification | Part | Action | What changed (summary) | Web edition |
|---|---|---|---|---|---|
| 2010-10-07 | G.S.R. 821(E) | Amended | Replaces 'Inspector' with 'Competent Person' wherever it occurs. | listed before the capture |
Possible IBR 2026 successors (heading match, unverified): Reg. 311, Reg. 382