Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)
Regulation 51 — Hydraulic test.
Text in the DPIIT web edition
Archived copy captured 03 Aug 2022 (Wayback Machine). This page was revised after the 2019 capture, so later amendments may be included. Units as printed.
| [image] | [image] |
| ||||||||||||||||
Earlier text: the 2008 DIPP web edition
MATERIALS OF CONSTRUCTION
SEAMLESS MOLYBDENUM STEEL BOILER AND SUPERHEATER TUBES FOR DESIGN METAL TEMPERATURES NOT EXCEEDING 510 DEGREE C (950 DEGREE F).
Hydraulic test
Each tube shall be tested at the Maker’s works on completion of manufacture and shall withstand a hydraulic pressure, to one and a half times the design pressure subject to a minimum of 0.70 kgf/mm2 but not greater than the pressure calculated by the following formula:
2 St
P = -----------
D
P = test pressure
D = outside diameter of the tube
Where t = nominal wall thickness of the tube
S = stress, which shall be taken as 40% of the minimum tensile strength at
room temperature.
(ii)Notwithstanding anything contained in clause (i), the hydraulic test for tubes in Makers’ premises may be dispensed with by the Inspecting Authority provided that the tubes are subject to non-destructive testing by an appropriate method like ultrasonic or/and Eddy current testing”.
Amendments found
Machine-assisted list from the amending notifications (DPIIT copies; 1990–1998 from scanned Gazette issues on India Code); may be incomplete.
| Date | Notification | Part | Action | What changed (summary) | Web edition |
|---|---|---|---|---|---|
| 2001-04-10 | G.S.R. 219 | Substituted | Replaced as part of the block substitution of regulations 36 to 56 (tube specifications). | listed before the capture | |
| 2004-08-02 | G.S.R. 265 | Amended | Revises the definition of stress S, adding a basis for austenitic stainless steel. | listed before the capture |