Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)
Regulation 46 — Hydraulic Test
Text in the DPIIT web edition
Archived copy captured 03 Aug 2022 (Wayback Machine). The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.
| Reg. 46 MATERIALS OF CONSTRUCTION SEAMLESS CARBON STEEL PIPES FOR HIGH TEMPERATURE SERVICE FOR DESIGN METAL TEMPERATURES NOT EXCEEDING 454 DEGREE C (850 DEGREE F) |
| (i) Each pipe shall be tested by the manufacturer and shall withstand a hydraulic pressure to one and half time the design pressure, but not greater than pressure calculated by the formula given below. In the absence of working pressure indicated in the Test Certificate then the test pressure indicated in the Test Certificate divided by 1.5 shall be the maximum working pressure. P = 2St/D where P = test pressure D = specified outside diameter of the pipe t = specified wall thickness of the pipe S = stress which shall be taken as 40% of the minimum tensile strength at room temperature. (ii) Notwithstanding anything contained in the above clause, the hydraulic test at the maker's works may be dispensed with provided that the pipes are subject to non destructive testing by an appropriate method like Ultrasonic or Eddy Current or Stray flux testing. |
Earlier text: the 2008 DIPP web edition
MATERIALS OF CONSTRUCTION
HOT FINISHED SEAMLESS CARBON STEEL BOILER AND SUPER-HEATER TUBES FOR DESIGN METAL TEMPERATURES NOT EXCEEDING 450°C (850 °F).
Hydraulic Test
Each tube shall be tested at the Maker’s works on completion of manufacture and shall
withstand a hydraulic pressure, to one and a half times the design pressure subject to a
minimum of 0.70 kgf/mm2 but not greater than the pressure calculated by the following
formula:
2 St
P = --------
D
Where, P = test pressure
D = outside diameter of the tube.
t = nominal wall thickness of the tube.
S = stress, which shall be taken as 40% of the minimum tensile strength of room temperature.
(ii)Notwithstanding anything contained in clause (i), the hydraulic test for tubes in maker’s premises may be dispensed with by the Inspecting Authority provided that the tubes are subjected to non-destructive testing by an appropriate method like ultrasonic or/and Eddy current testing.
Amendments found
Machine-assisted list from the amending notifications (DPIIT copies; 1990–1998 from scanned Gazette issues on India Code); may be incomplete.
| Date | Notification | Part | Action | What changed (summary) | Web edition |
|---|---|---|---|---|---|
| 2001-04-10 | G.S.R. 219 | Substituted | Replaced as part of the block substitution of regulations 36 to 56 (tube specifications). | listed before the capture | |
| 2008-06-27 | G.S.R. 123 OCR of scan | (i) | Omitted | Omits the sentence deriving working pressure from test pressure divided by 1.5. | listed before the capture |