Reg. 46
MATERIALS OF CONSTRUCTION

SEAMLESS CARBON STEEL PIPES FOR HIGH TEMPERATURE SERVICE FOR DESIGN METAL TEMPERATURES NOT EXCEEDING 454 DEGREE C (850 DEGREE F)

Hydraulic Test

(i) Each pipe shall be tested by the manufacturer and shall withstand a hydraulic pressure to one and half time the design pressure, but not greater than pressure calculated by the formula given below.  In the absence of working pressure  indicated in the Test Certificate then the test pressure indicated in the Test Certificate divided by 1.5 shall be the maximum working pressure.

                      P = 2St/D  

where   P  = test pressure

            D = specified outside diameter of the pipe

            t = specified wall thickness of the pipe

S = stress which shall be taken as 40% of the minimum tensile strength at room temperature.

(ii)  Notwithstanding anything contained in the above clause, the hydraulic test at the maker's works may be dispensed with provided that the pipes are subject to non destructive testing by an appropriate method like Ultrasonic or Eddy Current or Stray flux testing.

Earlier text: the 2008 DIPP web edition

MATERIALS OF CONSTRUCTION

HOT FINISHED SEAMLESS CARBON STEEL BOILER AND SUPER-HEATER TUBES FOR DESIGN METAL TEMPERATURES NOT EXCEEDING 450°C (850 °F).

Hydraulic Test

Each tube shall be tested at the Maker’s works on completion of manufacture and shall
withstand a hydraulic pressure, to one and a half times the design pressure subject to a
minimum of 0.70 kgf/mm2 but not greater than the pressure calculated by the following
formula:
                                   2 St
                                   P = --------
                                   D

Where, P = test pressure

D = outside diameter of the tube.

t = nominal wall thickness of the tube.

S = stress, which shall be taken as 40% of the minimum tensile strength of room temperature.

(ii)Notwithstanding anything contained in clause (i), the hydraulic test for tubes in maker’s premises may be dispensed with by the Inspecting Authority provided that the tubes are subjected to non-destructive testing by an appropriate method like ultrasonic or/and Eddy current testing.

Amendments found

Machine-assisted list from the amending notifications (DPIIT copies; 1990–1998 from scanned Gazette issues on India Code); may be incomplete.

DateNotificationPartActionWhat changed (summary)Web edition
2001-04-10G.S.R. 219SubstitutedReplaced as part of the block substitution of regulations 36 to 56 (tube specifications).listed before the capture
2008-06-27G.S.R. 123 OCR of scan(i)OmittedOmits the sentence deriving working pressure from test pressure divided by 1.5.listed before the capture