Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)
Regulation 42 — Hydraulic Test
Text in the DPIIT web edition
Archived copy captured 03 Aug 2022 (Wayback Machine). The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.
| Reg. 42 MATERIALS OF CONSTRUCTION COLD DRAWN SEAMLESS CAR BON STEEL BOILER, SUPERHEATER AND HEAT EXCHANGER TUBES FOR DESIGN METAL TEMPERATURES NOT EXCEEDING 454°C (850°F). |
| (i) Each tube shall be tested by the manufacturer and shall withstand a hydraulic pressure to one and half times the design pressure subject to a minimum of 1.00 kgf/mm2, but not greater than pressure calculated by the following formula. 2 S t
P = ------------
D where P = test pressure D = specified outside diameter of the tube t = specified wall thickness of the tube S = stress which shall be taken as 40% of the minimum tensile strength at room temperature. (ii) Notwithstanding any thing contained in the above clause, the hydraulic test at the maker’s works may be dispensed with, provided that the tubes are subject to non destructive testing by an appropriate method like Ultrasonic or Eddy Current or Stray Flux testing. |
Earlier text: the 2008 DIPP web edition
MATERIALS OF CONSTRUCTION
COLD DRAWN SEAMLESS STEEL BOILER AND SUPERHEATER TUBES FOR DESIGN METAL TEMPERATURES NOT EXCEEDING 454°C (850°F).
Hydraulic Test
Each tube shall be tested at the maker’s works on completion of manufacture and shall withstand a hydraulic pressure, to one and half times, the design pressure subject to a minimum of 0.70 kgf/mm2 but not greater than pressure calculated by the following formula:
2 St
P= ---------
D
where P = test pressure
D = outside diameter of the tube
t = nominal wall thickness of the tube
S = stress which shall be taken as 40% of the minimum tensile strength at room temperature.
(ii)Notwithstanding anything contained in clause (i), the hydraulic test for tubes in Makers’ premises may be dispensed with by the Inspecting Authority provided that the tubes are subject to non-destructive testing by an appropriate method like ultrasonic or/and Eddy current testing.
Amendments found
Machine-assisted list from the amending notifications (DPIIT copies; 1990–1998 from scanned Gazette issues on India Code); may be incomplete.
| Date | Notification | Part | Action | What changed (summary) | Web edition |
|---|---|---|---|---|---|
| 2001-04-10 | G.S.R. 219 | Substituted | Replaced as part of the block substitution of regulations 36 to 56 (tube specifications). | listed before the capture |