Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)
Regulation 392J
Text in the DPIIT web edition
Archived copy captured 03 Aug 2022 (Wayback Machine); the same page also prints regulations 392G, 392H, 392I. The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.
| Reg. 392 g, Reg. 392 h, Reg. 392 i, Reg. 392 j
Reg. 392 h
Reg. 392 i
Reg. 392 j
| |||||||||
Earlier text: the 2008 DIPP web edition
REGULATIONS FOR THE REGISTRATION OF BOILERS AND INSPECTION OF BOILERS AND STEAM-PIPES
Anti-collapse rings shall be of substantial section either of single or double angles bolted back to back with screw stays not less than 7/8th inch in diameter and about 7 inches in pitch passes through flat of angle and screwed into the Furnace, the ends being either rounded or riveted over on the fire side and fitted with nuts at the other. The stay bolts shall be fitted with ferrules not less than 1 inch in depth between furnace and angle ring.